HospitalInspections.org

Bringing transparency to federal inspections

1200 PLEASANT STREET

DES MOINES, IA 50309

No Description Available

Tag No.: K0011

Based on observations and interview, the facility failed to provide the 2 hour fire resistance separation between 2 different building types. This deficient practice would affect all residents within the affected zones. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Observations and interview on 4/10/12 through 4/12/12, revealed the following:

1. The North Tower 2 hour wall between the North Tower 2 and the North Main Lobby revealed a conduit penetration (approximately 1/4 inch in size) located above the suspended ceiling.

2. The North Tower 1st Floor 2 hour wall by the Younker Connector revealed a pipe & communications line penetration (approximately 3/16 inch in size) located above the suspended ceiling.

3. The North Tower Level A 2 hour fire wall to Blank Hospital revealed a wire bundle penetration (approximately 1/4 inch in size) located above the suspended ceiling.

4. The North Tower Level B 2 hour fire wall between the North Wing and the South Wing revealed a pipe penetration (approximately 4 inches in size), a hole (approximately 1 inch in size) located above the suspended ceiling.

5. The North Tower Level C 2 hour Fire Wall in Radiology by the Men's Locker Room revealed a blue pipe penetration (approximately 1/4 inch in size) located above the suspended ceiling.

6. The Northeast Addition Middle Corridor 2 hour Fire Wall revealed a conduit penetration (approximately 1/4 inch in size) located above the suspended ceiling.

7. The Northeast Addition 2nd Floor 2 hour Fire Wall by the Pharmacy revealed a conduit penetration (approximately 3/16 inch in size) located above the suspended ceiling.

8. The Blank Hospital Level C 2 hour wall to the North Wing revealed a pipe penetration (approximately 1/4 inch in size).

The Facility Maintenance Staff A confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0012

Based on observations and staff interview, it was determined the facility was a 6 story building and consisted of fire resistant construction equipped with an automatic sprinkler system. The facility failed to assure minimum building construction requirements were maintained by ensuring that holes and gaps around penetrations are sealed with one-hour fire rated materials to protect the adjacent floors. This deficient practice affects all residents within the affected zones. The facility had a capacity of 674 residents and a census of 363 residents at the time of inspection.

Findings include:

Observations and interview on 4/10/12, revealed the following;

1. The North Tower 6th Floor Room N669 revealed a vertical sprinkler head (1 of 2) penetration (approximately 1/2 inch in size) located in the ceiling lid above the Bed.

2. The North Tower 5th Floor Room N563 revealed a vertical sprinkler head penetration (approximately 1/2 inch in size) located in the ceiling lid above the Bed.

3. The North Tower 5th Floor by Room 565 revealed a vertical sprinkler head penetration (approximately 1/2 inch in size) due to a sprinkler escutcheon ring falling off the head.

4. The North Tower 4th Floor Room 460 revealed a vertical sprinkler head penetration (approximately 1/2 inch in size) located by the Chair.

5. The North Tower 4th Floor Nurse's Station revealed a vertical sprinkler head penetration (approximately 1/2 inch in size) located by the Medication Room N-424.

6. The North Tower 4th Floor by the Environmental Closet revealed a vertical gap (approximately 1/4 inch in size) located around the sprinkler head.

7. The North Tower 3rd Floor Room N377 revealed a vertical sprinkler penetration (approximately 1 inch in size) located above the Bed.

8. The North Tower Control Room 11 revealed a vertical sprinkler penetration (approximately 1/2 inch in size) located in the ceiling lid.

9. The North Tower 7th Floor Megavator Room revealed a missing piece of drywall (approximately 2 feet by 7 feet in size) off the wall. The absence of the drywall leaves the inner wall structure exposed. Maintenance Staff A indicated that the facility was in the process of repairing a leak in the roof of this area.

10. The North Tower 4th Floor revealed that the baseboard was missing from the bottom of all of the Corridor Walls throughout the floor.

11. The North Tower 3rd Floor Electrical Closet revealed an open pipe penetration (approximately 2 inches in size), extending through the wall of the North Tower.

12. The Microbiology Compressed Gas Storage Room revealed 4 penetrations (approximately 3/16 inch in size each) located around lines extending through the ceiling, a vertical insulated pipe penetration (approximately 3/16 inch in size) through the ceiling, and 2 vertical holes (approximately 1 inch in size each) located in the ceiling.

13. The Dietician's Office revealed a sprinkler pipe penetration (approximately 1/2 inch in size).

14. The Cooler #23 revealed a sprinkler pipe penetration (approximately 1/2 inch in size) into a resident's room.

15. The Level D EVS Break Room revealed 3 sprinkler pipe penetrations (approximately 1/2 inch in size each).

16. The MOB 1 Children's Health Center Cubicle Office Area revealed a vertical hole (approximately 1/2 inch in size) in the tile around the sprinkler head.

The Facility Safety Supervisor and Maintenance Staff B confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0017

Based on observation and interview, the facility failed to maintain 1 corridor room wall properly separated from the corridor. This deficient practice could affect all residents within the affected zone. The facility had a capacity of 674 residents and a census of 363 residents at the time of inspection.

Findings include:

Observation and interview on 4/10/12, revealed a white wire penetration (approximately 1/4 inch in size) located in the corridor wall of the IT/Communications Room of the North Building 4th Floor. The Facility Safety Supervisor confirmed this finding on the date of inspection

No Description Available

Tag No.: K0018

Based on observations and interview, the facility failed to maintain 2 doors in 1 smoke zone in proper working condition. This deficient practice would affect all st within the affected zones. The facility had a capacity of 674 residents and a census of 363 residents on the date of inspection.

Findings include:

Observations and interview on 4/10/12, revealed the following:

1. The North Tower Level C Supervisor of Radiology Office Door revealed a kick down device on the door to prevent the door from swinging closed.

2. The North Tower Level C PACS Office Door revealed a kick down device on the door to prevent the door from swinging closed.

3. The Blank Hospital 6th Floor Restroom by Room 503A revealed the door failed to close and latch properly into the door frame with the swing of the door closer.

4. The Blank Hospital 6th Floor Door to the Laundry Room 516 revealed the door was obstructed from opening fully due to a cart blocking the door.

5. The Blank Hospital 6th Floor Physician's Lounge 555 revealed a garbage can propping open the door to the Sleep Room Hallway.

6. The Anna Blank Clinic Conference Room LL04 revealed the door failed to close and latch properly into the door frame with the swing of the door closer.

The Facility Safety Supervisor confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0020

Based on observation and interview, the facility failed to maintain proper 1 hour vertical fire separation in 1 location. This deficient practice could affect all residents within the affected zone. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Observation and interview on 4/11/12, revealed a center flexible conduit penetration (approximately 1/2 inch in size) located in the Corridor Wall to the Stairwell of Younker 3rd Floor by the Transition by Audiology. The Facility Maintenance Staff A confirmed this finding on the date of inspection.

No Description Available

Tag No.: K0025

Based on observations and interview, the facility failed to maintain smoke barriers in accordance with National Fire Protection Association (NFPA) Standard 101, 2000 edition, 19.3.7.3. Smoke barriers shall be continuous from outside wall to outside wall and from floor to a roof extending through all concealed spaces. Smoke barriers shall have a fire resistance rating of not less than 1/2 hour. This deficient practice affects all residents and staff within the affected zones. This facility has a capacity of 674 and a census of 363 residents.

Findings include:

Observations and interview on 4/11/12, revealed the following:

1. The Powell 4th Floor Smoke Barrier by Room P-438 revealed a pipe penetration (approximately 4 inches in size) located above the suspended ceiling.

2. The Powell 4th Floor Smoke Barrier by Room P439 revealed a pipe penetration (approximately 1/4 inch in size) located above the suspended ceiling.

3. The Powell 3rd Floor Smoke Barrier Wall #MP0000078 revealed a pipe penetration (approximately 4 inches in size) located above the suspended ceiling.

4. The Powell 3rd Floor Smoke Barrier Wall #MP0000077 revealed a pipe penetration (approximately 4 inches in size) located above the suspended ceiling.

The Facility Maintenance Staff A confirmed this finding on the date of inspection.

No Description Available

Tag No.: K0027

Based on observation and interview, the facility failed to maintain smoke barrier doors in proper working condition. This deficient practice would affect all residents within the affected zone. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Observation and interview on 4/11/12, revealed the Younker 5th Floor Smoke Barrier Doors by Room 515 failed to close and latch properly into the door frame with the swing of the door closers. The Facility Maintenance Staff A confirmed this finding on the date of inspection.

No Description Available

Tag No.: K0029

Based on observation and staff interview, the facility failed to provide separation of hazardous areas from other compartments in accordance with National Fire Protection Association (NFPA) Standard 101, The Life Safety Code, 2000 edition, 19.3.2.1. This deficient practice would affect allresidents within the affected zones. The facility had a capacity of 674 residents and a census of 363 residents.


Findings include:

Observation and interview on 4/11/12, revealed the Younkers 7th Floor Equipment Room by Room 717 door failed to close and latch properly into the door frame with the swing of the door closer. The Facility Maintenance Staff A confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0038

Based on observations and interview, the facility failed to maintain exit pathways that were clear, unobstructed, and easily accessible at all times. This deficient practice would affect all residents within the affected zones. The facility had a capacity of 674 residents and census of 363 residents on the date of inspection.

Findings include:

Observations and interview on 4/10/12, revealed the following:

1. The 5th Floor of the North Building revealed Hinged Nursing Charting Stations attached to the walls that failed to be self-closing when pressure was released.

2. The North Building 3rd Floor Corridor revealed Hinged Charting Stations attached to the walls that failed to be self-closing when pressure was released.

3. The MOB1 Children's Health Center Doctor's Office Hallway revealed a chair in the Hallway.

4. The Anna Blank Clinic Basement Mechanical Door revealed the door failed to open when tested.

5. The Ankeny Blank Pediatrics Therapy revealed the 2 Northeast Mechanical Room Doors were closed and latched with slide locks that would not allow for access to an exit from the interior of the room. This building was inspected on 4/17/12.

The Facility Safety Supervisor confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0046

Based on observations and interview, the facility failed to maintain several emergency lighting units within the facility in proper working condition. This deficient practice would affect all residents and staff members within the affected zones. The facility had a capacity of 674 residents and census of 363 residents.

Findings include:

Observations and interview on 4/12/12, revealed the following:

1. The Blank Infusion Center Corridor by the Front Desk revealed the emergency lighting unit failed to illuminate when tested.

2. The Blank Infusion Center Corridor by Room 3 revealed the emergency lighting unit failed to illuminate when tested.

3. The Blank Infusion Center Corridor by Room 5 revealed the emergency lighting unit failed to illuminate when tested.

4. The Store Room "D" revealed the emergency lighting unit on the west side of the concrete pillar failed to illuminate when tested.

5. The Outpatient Therapy South revealed the emergency lighting unit located next to the Restroom failed to illuminate when tested. This building was inspected on 4/17/12.

The Facility Maintenance Staff A confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0047

Based on observations and interview, the facility failed to assure exit signs were properly displayed and visible throughout the facility in 2 locations. This deficient practice affects 1 smoke zone. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Observations and interview on 4/11/12, revealed the following:

1. The facility failed to provide visible illuminated exit signs to indicate the path of egress in the middle of the East Hall, on the West Side of the smoke barriers on the 2nd, 3rd, 4th, and 5th Floors.

2. The West Des Moines Blank Pediatric Therapy revealed the exit sign by the Soiled Utility Room did not indicate egress to the West Exit Door due to the arrowed chevron not being removed.

Maintenance Staff A confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0050

Based on record review and interview, the facility failed to provide fire drills of varied times of the day for 4 of 4 quarters review. This deficient practice would affect all residents within the facility. The facility had a capacity of 83 residents and a census of 23 residents on the date of inspection.

Findings include:

Record review and interview on 4/10/12, revealed the facility Fire Drill documentation for the Methodist West Hospital showed that 4 of the 3rd Shift drills were conducted at approximately the same time. The Third Shifts were conducted as follows: 3/6/11 at 10:51 p.m., on 6/7/11 at 1043 p.m., on 9/9/11 at 10:50 p.m., and on 12/18/11 at 10:53 p.m. The Facility Maintenance Staff A confirmed this finding.

No Description Available

Tag No.: K0052

Based on observations, record review, and interview, the facility failed to maintain the building's fire alarm system in accordance with the National Fire Protection Association (NFPA) Standard 72, National Fire Alarm Code, 1999 edition. This deficient practice would affect all residents within the affected zones. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Observations, record review, and interview on 4/10/12, revealed

1. The North Building 2nd Floor Intern's Lounge revealed a smoke detector that was installed within 3 feet of an air diffuser.

2. The Fire Alarm Panel located in the North Tower 3rd Floor Electrical Closet indicated that the system was in trouble. Maintenance Staff A indicated that the problem was a bad smoke detector.

3. The North Tower 4th Floor revealed a smoke detector covered with blue painter's tape in Room 479.

4. The Outpatient Infusion Area revealed a smoke detector that was installed within 3 feet of an air diffuser in the Corridor.

5. The Wound Healing Center by Exam Room 1 revealed a smoke detector that was installed within 3 feet of an air diffuser.

6. The North Tower Level A Mechanical Room revealed the Fire Alarm Control Panel circuit breaker located in Electrical Panel ELSA 120 B01 was not properly locked out.

7. The Blank Hospital 1st Floor across from the Physician's Neonatal Locker Room revealed a smoke detector that was installed within 3 feet of an air diffuser.

8. The MOB1 Children's Health Center Southwest Doctor's Office Corridor revealed a smoke detector installed within 3 feet of an air diffuser.

9. The MOB1 Children's Health Center Nurse's Station revealed a smoke detector installed within 3 feet of an air diffuser.

10. The MOB1 Children's Health Center East Weight Room Hallway revealed a smoke detector that was installed within 3 feet of an air diffuser.

11. The MOB1 Children's Health Center East Waiting Room Area revealed a smoke detector that was installed within 3 feet of an air diffuser.

12. The Methodist West Hospital 5th Floor Corridor by Room 5057 revealed a smoke detector that was installed within 3 feet of an air diffuser. This facility had a capacity of 83 residents and a census of 23 residents.

13. The West Des Moines Blank Pediatrics Therapy revealed the facility provided only an annual inspection of the building's Fire Alarm System.

The Facility Maintenance Staff A and B confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0056

Based on observation and interview, the facility failed to provide proper sprinkler protection in 1 location within the facility in accordance with the National Fire Protection Association (NFPA) 13, Standard for the Installation of Sprinkler System, 1999 edition. This deficient practice would affect all residents and staff in the affected zone. The facility had a capacity of 674 residents and a census of 363 residents on the date of inspection.

Findings include:

Observation and interview on 4/11/12, revealed a mixture of a quick response sprinkler head and standard response sprinkler head in the Younkers 4th Floor EVS Closet on the East end of the West Hall. This room also revealed the two sprinkler heads were installed within 6 feet of each other. The Facility Maintenance Staff A confirmed this finding on the date of inspection.

No Description Available

Tag No.: K0062

Based on observations and interview, the facility failed to maintain the building's sprinkler system in accordance with the National Fire Protection Association (NFPA) Standard 25, Standard for the Inspections, Testing, and Maintenance for Sprinkler Systems, 1999 edition. This deficient practice would affect all residents within the affected zones. The facility had a capacity of 674 residents and a census of 363 residents on the date of inspection.

Findings include:

Observations and interview on 4/11/12, revealed the following:

1. The Younkers 4th Floor Younkerville revealed a gap between the sprinkler head and the ceiling tile located above the East Therapy Mat by the "Smiley Face" ceiling tile.

2. The Younkers 4th Floor Younkerville revealed "branches" off the fake tree were within 18 inches of sprinkler heads located in the center of the room.

The Facility Maintenance Staff A confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0064

Based on observations and interview, the facility failed to maintain fire extinguishers in the building in accordance with the National Fire Protection Association (NFPA) 10, Standard for Portable Fire Extinguishers, 1998 edition. This deficient practice would affect all residents and staff within the affected zones. The facility had a capacity of 674 residents and a census of 363 residents on the date of inspection.

Findings include:

Observations and interview on 4/10/12 and 4/11/12, revealed the following:

1. The North Tower 7th Floor North Mechanical Room revealed 3 fire extinguishers that were missing the March 2012 monthly visual inspection.

2. The North Tower 7th Floor West Elevator Equipment Room revealed a fire extinguisher that was sitting on the floor and was not properly mounted. This extinguisher did not receive the March 2012 monthly visual inspection.

3. The North Tower 7th Floor Main Lobby Elevator Penthouse revealed the extinguisher was not provided with the March 2012 monthly visual inspection.

4. The North Tower Helipad North Stairwell revealed the fire extinguisher was missing the March 2012 monthly visual inspection.

5. The North Tower North 9 Elevator Penthouse revealed the fire extinguisher was sitting on the ground and was not properly mounted. This fire extinguisher also revealed missing February and March 2012 monthly visuals.

6. The North Tower Laboratory Break Room revealed a fire extinguisher that was not mounted and was not provided with an inspection tag to identify the date of the last annual inspection.

7. The North Tower Laboratory Immunohematology Room revealed the fire extinguisher was obstructed by testing equipment.

8. The North Tower Cath Laboratory Mechanical Room revealed a "General" Brand fire extinguisher that was on recall.

9. The North Tower 7th Floor Mechanical Room revealed a "General" Brand fire extinguishers that was on recall.

10. The North Tower Life Flight Machine Shed revealed a "General" Brand fire extinguisher that was on recall. Documentation on the fire extinguisher indicated that the extinguisher was missing a March 2012 monthly visual inspection. This extinguisher was also mounted where the top of the extinguisher was at a height more than 5 feet off the ground.

11. The North Tower 3rd Floor Corridor by Room N301 revealed the fire extinguisher was missing the March 2012 monthly visual inspection.

12. The Laboratory revealed the facility failed to provide the February and March 2012 monthly visual inspections for fire extinguisher #PO4022.

13. The Northeast Addition-Northeast Elevator Penthouse revealed the fire extinguisher was missing the March 2012 monthly visual inspection.

The Facility Maintenance Staff A and B confirmed these findings on the date of inspection

No Description Available

Tag No.: K0074

Based on observation and interview, the facility failed to provide curtains or blinds that were flame retardant materials, in 1 location, meeting the provisions of 10.3.1 of the National Fire Protection Association (NFPA) Standard 101, Life Safety Code, 2000 edition. This deficient practice would affect all residents within the affected zone. The facility had a capacity of 674 residents and a census of 363 residents on the date of inspection.

Findings include:

Observation and interview on 4/11/12, revealed a vinyl mini-blind located on the window in the Blank Hospital Control Room. The Facility Maintenance Staff A confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0130

(A) Based on observations and interview, the facility failed to properly maintain the building's suspended ceiling grid in proper working condition. This deficient practice would affect all residents and staff within the affected zones. The facility had a capacity of 674 residents and a census of 363 residents on the dates of inspection.

Findings include:

Observations and interview on 4/10/12 through 4/12/12, revealed the following:

1. The Emergency Department Ambulance Garage revealed multiple suspended ceiling tiles missing on by the North Garage Door, the Southeast Corner of the Garage, and by the East Garage Door.

2. The North Tower 7th Floor Medical Personal Storage Room revealed a broken ceiling tile that revealed a gap (approximately 1/2 inch in size) in the ceiling tile grid.

3. The Microbiology Laboratory revealed communication lines running through the ceiling tile grid that left a gap (approximately 1/2 inch in size) in the ceiling tile grid.

4. The Blank Hospital Level A Utility Closet by Phlebotomy revealed several suspended ceiling tiles were missing.

5. The MOB1 Children's Health Center Clinic EVS Room revealed several missing smoke ceiling tiles in the grid.

The Facility Maintenance Staff A and B confirmed these findings on the dates of inspection.

(B) Based on observation and interview, the facility failed to maintain proper storage of 1 compressed helium bottle in 1 location. This deficient practice would affect all residents and staff within the affected zone. The facility had a capacity of 674 residents and a census of 363 residents on the dates of inspection.

Findings include:

Observation and interview on 4/10/12, revealed an unsecured helium tank in the North Tower Gift Shop Storage Room. The Facility Maintenance Staff A confirmed this finding on the date of inspection.

(C) Based on observation and interview, the facility failed to remove all unapproved air freshner devices within the facility. This deficient practice would affect all residents within the affected zone. The facility had a capacity of 674 residents and a census of 363 residents on the dates of inspection.

Findings include:

Observation and interview on 4/12/12 revealed a heated oil air freshner that plugged directly into the wall was in use in the MOB1 Children's Health Center Scheduling Office. The Facility Maintenance Staff A confirmed this finding on the date of inspection.

No Description Available

Tag No.: K0144

Based on record review and interview, the facility failed to provide proper testing and documentation of the building's emergency generator in accordance with the National Fire Protection Association (NFPA) Standard 110, 1999 edition. This deficient practice would affect all residents throughout the facility. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Record review and interview on 4/10/12, revealed that the monthly 30-minute load tests were conducted at 17% of the name plate. This did not meet the 30 minutes under load at 30% of the name plate. The Facility Maintenance Staff A confirmed this finding on the date of inspection.

No Description Available

Tag No.: K0147

Based on observations and interview, the facility failed to maintain the building's electrical system in accordance with the National Fire Protection Association (NFPA) Standard 70, National Electrical Code, 1999 edition. This deficient practice would affect all residents within the affected zones. The facility had a capacity of 674 residents and had a census of 363 residents on the date of inspection.

Findings include:

Observations and interview on 4/10/12 to 4/12/12 revealed the following:

1. The North Tower 6th Floor Main Lobby Elevator Penthouse revealed a fan plugged into a drop cord.

2. The North Tower 5th Floor Menu Room by N557 revealed permanently used fluorescent lighting that was not hardwired.

3. The North Tower 4th Floor Office N401 revealed an extension cord with a coffee pot plugged into it.

4. The Emergency Department Ambulance Garage East Garage Door revealed a missing cover device for the exposed electrical wiring in the Garage Door Opener.

5. The North Tower Level A Mechanical Room A revealed a drop cord that was in use in the A.H. Unit S3.

6. The North Tower Level A Mechanical Room A revealed 3 electrical junction boxes on the ceiling lid by the Electrical Distribution Panels that were not properly covered.

7. The North Tower 3rd Floor Locker Room revealed an electrical outlet that was not provided with ground fault circuit interruption and was installed within 6 feet of a sink.

8. The North Tower Level A Mechanical Room revealed an open gap in Electrical Panel P-B1.

9. The North Tower Level A 2 Hour Fire Wall near the Environmental Closet revealed an open electrical junction box without a cover located above the suspended ceiling tile.

10. Room S408 revealed a lamp plugged into a surge protector.

11. Room S231 revealed the Ground Fault Circuit Interrupter was faulty.

12. The Dialysis Break Room revealed a coffee pot and a refrigerator plugged into a surge protector.

13. The Blank Hospital Flow Cytometry Laboratory revealed a refrigerator plugged into a surge protector.

14. The Anna Blank Clinic Office LL20 revealed a lamp plugged into an extension cord.

15. The MOB1 Children's Health Center East Weight Room revealed a broken electrical outlet cover.

16. The Methodist West Hospital 3rd Floor Team Member Break Room revealed the facility failed to maintain the Ground Fault Circuit Interrupters in the West wall by the sink. The Ground Fault Circuit Interrupter electrical outlets failed to trip when tested and contained an open neutral. This building had a capacity of 83 residents and census of 23 residents at the time inspection.

17. The Methodist West Hospital Break Room Pharmacy revealed the facility failed to provide Ground Fault Circuit Interruptors for the electrical outlets next to the sink on the West wall. This building had a capacity of 83 residents and a census of 23 residents at the time of inspection.

The Facility Maintenance Staff A and B confirmed these findings on the date of inspection.

No Description Available

Tag No.: K0154

Based on record review and interview, the facility failed to provide proper fire watch policy documentation for the sprinkler system outage policy. This deficient practice would affect all residents throughout the facility. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Record review and interview on 4/12/12, revealed the facility's Sprinkler System Outage Policy for both Methodist West Hospital and the Methodist Main Hospital failed to provide contact information for the local Fire Department, the Iowa Department of Inspections and Appeals, the State Fire Marshal's Office, and the facility's Insurance Company. Contact information and phone numbers are required to be listed in the Sprinkler System Outage Policy. The Facility Maintenance Staff A confirmed this finding on the date of inspection.

No Description Available

Tag No.: K0155

Based on record review and interview, the facility failed to provide proper fire watch policy documentation for the fire alarm outage policy. This deficient practice would affect all residents throughout the facility. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Record review and interview on 4/12/12, revealed the facility's Fire Alarm Outage Policy for both Methodist West Hospital and the Methodist Main Hospital failed to provide contact information for the local Fire Department, the Iowa Department of Inspections and Appeals, the State Fire Marshal's Office, and the facility's Insurance Company. Contact information and phone numbers are required to be listed in the Fire Alarm Outage Policy. The Facility Maintenance Staff A confirmed this finding on the date of inspection.

Means of Egress - General

Tag No.: K0211

Based on observation and interview, the facility failed to maintain 1 Alcohol-Based Hand Rub in accordance with Section 19.3.2.7 of the 2000 Life Safety Code. This deficient practice affects 1 smoke zone. The facility had a capacity of 674 residents and a census of 363 residents.

Findings include:

Observation and interview on 4/11/12, revealed an alcohol based hand rub dispenser located above an electrical source in Room S312. Maintenance Staff A verified this observation on the date of inspection.