Fire Alarm System - Installation

Tag No.: K0341

Based on observation and staff interview, the facility failed to provide documentation that the fire alarm system was connected to a central receiving station. This deficient practice had the potential to delay or prevent fire department notification in the event of an emergency.

Finding are:
Observation and staff interview on 2-7-2024 at 10:45 AM revealed the following:

During record review no central receiving station logs were provided.

During interview on 2-7-2024 at 10:45 AM, Administrative Staff A and Maintenance Staff B confirmed no central receiving station logs were provided.

Fire Drills

Tag No.: K0712

Based on record review and staff interview, the facility failed to conduct fire drills for each shift. These conditions did not provide simulated training for staff to respond to a fire emergency during various activities and staffing levels.

Findings are:
Record review on 2-7-2024 at 10:00 AM revealed the following:

1. A fire drill was not recorded on the 1st shift of the 2nd quarter of 2023 (April-June)
2. A fire drill was not recorded on the 3rd shift of the 3rd quarter of 2023 (July-Sept.)
3. No fire drills have been recorded for all 3 shifts of the 4th quarter of 2023 (Oct.-Dec.)

During an interview on 2-7-2023 at 10:00 AM Administrative Staff A and Maintenance Staff B confirmed the fire drills had not been conducted.