Tag No.: K0017
Based on observation, it was determined that the facility failed to ensure that corridor walls are smoke resistive.
Findings include:
On 1/6/14 at 12:00 PM, in the presence of Staff #4, there were three penetrations in the smoke rated wall in the Stress Testing Room.
Tag No.: K0018
Based on observation, it was determined that the facility failed to ensure that there are no impediments to closing of doors.
Findings include:
On 1/6/14 at 10:30 AM, in the presence of Staff #4, the Receiving Room door was blocked open with a brick, preventing the automatic closing of the door.
Tag No.: K0034
Based on observation, it was determined that the facility failed to ensure that stairwells are maintained in accordance with Life Safety Code (LSC) 7.2.
Findings include:
On 1/6/14 at 10:40 AM, in the presence of Staff #4, there was storage of materials in Stairwell #4, #5, and #6.
Tag No.: K0039
Based on observation, it was determined that the facility failed to ensure that corridors are maintained clear and unobstructed.
Findings include:
On 1/6/14 at 10:55 AM, in the presence of Staff #4, the exit access in the Kitchen was reduced from the required 4 feet to 2 feet, due to a cart blocking the access.
Tag No.: K0072
Based on observation, it was determined that the facility failed to ensure that exit doors can be opened in the event of an emergency.
Findings include:
1. On 1/6/14 at 11:10 AM, in the presence of Staff #4, the exit door to the Doctor's Parking Lot did not instantly open.
2. On 1/6/14 at 12:05 PM, in the presence of Staff #4, the exit door in the hallway to the MRI Trailer, did not instantly open.
Tag No.: K0211
Based on observation, it was determined that the facility failed to ensure that alcohol based hand rub (ABHR) dispensers are not installed above ignition sources.
Findings include:
1. On 1/6/14 at 10:30 AM, in the presence of Staff #4, an ABHR was mounted above an electrical outlet in the pre-admission corridor.
2. On 1/9/14 at 10:10 AM, in the presence of Staff #4, an ABHR was mounted above an electrical outlet in Room #303.
3. On 1/9/14 at 10:25 AM, in the presence of Staff #4, an ABHR was mounted above an electrical outlet in Room #304.
4. On 1/9/14 at 10:30 AM, in the presence of Staff #4, an ABHR was mounted above an electrical outlet in Room #310.
5. On 1/9/14 at 11:05 AM, in the presence of Staff #4, an ABHR was mounted above an electrical outlet in Nursery #1.
6. On 1/9/14 at 11:25 AM, in the presence of Staff #4, an ABHR was mounted above an electrical outlet in Room #488.