Tag No.: K0033

1) The facility failed to ensure exits are arranged to provide a continuous path of escape.

Observation determined the access to the east stair enclosure on the fourth (4th) and fifth (5th) floor was through intervening spaces. The fourth (4th) floor must exit through the Surgical Suite and the fifth (5th) floor must exit through the PT/OT Suite to reach the east stair enclosure.
2) The 5th floor east stair enclosure wall between the PT/OT suite and the stairway terminated at the ceiling.
3) The door installed in the east basement stair enclosure had no label indicating the fire protection rating of the wood door.