HospitalInspections.org

Bringing transparency to federal inspections

35 MILES STREET

DAMARISCOTTA, ME 04543

No Description Available

Tag No.: K0029

While surveying the facility with the safety manager and vice president of operations, the inspector observed that the self-closing device had been removed from the 60 minute rated fire door assembly serving as an opening protective for the lab (hazard) area. The door also serves as the entrance for the blood draw area of the lab.

No Description Available

Tag No.: K0056

While surveying the facility with the safety manager and vice president of operations, the inspector observed that no fire sprinkler protection was present in the enclosed main entrance/exit serving the hospital building.