The information below comes from the statement of deficiencies compiled by health inspectors and provided to AHCJ by the Centers for Medicare and Medicaid Services. It does not include the steps the hospital plans to take to fix the problem, known as a plan of correction. For that information, you should contact the hospital, your state health department or CMS. Accessing the document may require you to file a Freedom of Information Request. Information on doing so is available here.

BECKLEY ARH HOSPITAL 306 STANAFORD ROAD BECKLEY, WV 25801 April 19, 2016
VIOLATION: MAINTENANCE OF PHYSICAL PLANT Tag No: A0701
Based on observation and staff interview, it was determined the hospital failed to ensure the condition of the physical environment is maintained in a manner that assures the safety and well-being of the patients it serves.

Findings include:

1. A review of the Maintenance Work Order book revealed the air handler filters for the Behavioral Health Unit were last changed on 5/14/15.

2. During a brief interview with the Engineering Manager on 4/19/16 at approximately 8:30 a.m. he stated the scheduled preventive maintenance for air handler filter changes are expected to occur quarterly (every three (3) months). He agreed that the filters were not changed as required on 11/4/15 and 2/4/16.

3. During a facility tour on 4/19/16 between 9:00 a.m. and 11:30 a.m. an inspection of the air handler supplying the Behavioral Health Unit revealed the filters for the air handler were last changed on 8/4/15. Documentation of this filter change was not recorded in the Maintenance Work Order book.

4. The above findings were discussed during the tour with the facility Administrator and the Engineering Manger and they agreed with the findings. Both stated this issue would be corrected to ensure compliance with the federal regulations.