Tag No.: K0027
Based on observation and interview, it was determined the facility failed to maintain door openings in smoke barrier walls in two instances within the facility.
Findings include:
1. Observation on March 12, 2015, at 10:45 AM revealed:
a. 10:45 AM - The 1st floor smoke barrier door located on the Medical Storage room lacked a self -closing device.
b. 10:55 AM - The 1st floor cross corridor smoke barrier door located near the Medical Records room did not close entirely when released from the hold open magnet.
Exit interview with facility representative #1 on March 12, 2015, between 12:50 PM and 1:00 PM confirmed the smoke barrier door deficiencies.
Tag No.: K0038
Based on observation and interview, it was determined the facility failed to ensure exit access corridors were maintained clear and unobstructed within the facility.
Findings include:
1. Observation on March 12, 2015, at 12:05 PM revealed several linen carts stored in the corridor located in the lower level Clean Linen Process room.
Exit interview with facility representative #1 on March 12, 2015, between 12:50 PM and 1:00 PM confirmed the items stored in the corridor.
Tag No.: K0144
Based on documentation review, observation, and interview, it was determined the facility failed to maintain the emergency generator in two instances within the facility.
Findings include:
1. Documentation review on March 12, 2015, at 8:35 AM revealed the weekly electrolyte level checks were not performed on the emergency generator batteries for the entire past year.
Exit interview with facility representative #1 on March 12, 2015, between 12:50 PM and 1:00 PM confirmed the lack of documentation.
2. Observation on March 12, 2015, at 9:05 AM revealed the generator location had not maintained a minimum of 30 inches of working space around the unit.
Exit interview with facility representative #1 on March 12, 2015, between 12:50 PM and 1:00 PM confirmed the lack of working space.