Tag No.: K0144
Morris County
Based on document review, it was determined that the facility failed to ensure that the monthly generator exercise test is documented in accordance with NFPA 99.
Findings include:
On 11/29/12 at 11:30 AM, the monthly generator test documentation was reviewed in the presence of Staff #1. There was no evidence of the Automatic Transfer Time during the monthly tests.