Bringing transparency to federal inspections
Tag No.: K0132
Based upon observation, building separations between Healthcare and non-Healthcare occupancies are not maintained in accordance with Code requirements. Failure to maintain required separations can put occupants at risk to exposure from a fire occuring in the adjacent occupancy.
Findings include:
A. On 4/17/19 while in the company of the DMCE, it was observed that not all doors in the 4-hour barriers separating the non-Healthcare Buildings from the Healthcare Kellogg Building were maintained to self-close to a latched condition to comply with 8.3.3.1 and NFPA 80.
Locations observed include:
1. At 9:40 AM, at the 2nd floor near the West elevators separating the Pavilion Building.
2. At 9:50 AM, at the 1st floor Northwest set of doors, Southwest set of doors, and the Far Southwest set of doors separating the Pavilion Building.
3. At 10:05 AM, at the 1st floor South set of doors separating the Jelke Building.
Tag No.: K0161
Based upon observation, not all building structural components are protected to afford the required fire rating. Failure to provide protection can result in premature failure of the building structural components if a fire event occured.
Finding includes:
On 4/17/19 at 3:00 PM while in the company of the PM an unprotected steel beam was observed lacking fire proofing for approximately 3'-0". This condition does not comply with the requirements of 19.1.2.3 as being constructed of materials which maintain a 2-hour fire resistant rating. Location observed: Fifth floor East end of corridor AP-5017 leading to Surgery. Beam is above suspended acoustical tile soffited ceiling.
Tag No.: K0211
Based upon observation, means of egress components are not maintained in accordance with Code requirements. Failure to maintain means of egress can compromise the safety of occupants during required exiting of the building.
Findings include:
A. On 4/17/19 at 3:15 PM while in the company of the DMCE it was observed at the 3rd floor exit access door from the tenant suite which serves an occupant load greater than three, that a dead bolt lock was utilized in addition to the lockset, thereby not in compliance with 7.2.1.5.10.6.
B. On 4/17/19 at 3:30 PM while in the company of the DMCE it was observed at the ground floor discharge level of Stair "B" that an interrupter gate was not provided to comply with 7.7.3.4 to prevent occupants from continuing to the lower levels of the building during exiting.
C. On 4/17/19 at 3:35 PM while in the company of the DMCE it was observed at the discharge level of Stair "B" that an Exit Passageway was utilized to reach the exterior door of the building. The Exit Passageway had two tubs identified for shredded paper collection stationed in the Exit Passageway in non-compliance with 7.2.6.1 and 7.1.3.2.3.
Tag No.: K0222
Based on observation, not all egress doors are installed and maintained as required. This deficient practice could affect occupants using the egress paths because their egress under emergency conditions could be impeded if they are not properly installed and maintained.
Findings include:
A. On 4/16/19 at 10:35 AM, while in the company of the DMCE, it was observed at the Business occupancy 12th floor south wing that exit signage was not provided to identify access to the second exit from the floor to comply with 39.2.4.1 and 39.2.10.
B. On 4/16/19 at 10:37 AM, while in the company of the DMCE, it was observed that magnetic locking devices where installed on cross corridor doors in the south wing of the 12th floor. The magnets were not active at the time of the inspection but permanent disablement could not be confirmed because components which could become functional appeared to be installed. The doors were not provided with the required signage to comply with 7.2.1.6.1.1(4) in accordance with Delayed Egress locking devices as permitted by 39.2.2.2.5 or sensors and manual release buttons to comply with 7.2.1.6.2(1) & (3) in accordance with Access Controlled Egress systems as permitted by 39.2.2.2.6.
C. On 4/16/19 at 11:15 AM, while in the company of the DMCE, it was observed that Exit signage is provided at doors equipped with magnetic locking devices at the cross corridor doors of the 8th floor Kellogg Node which indicated the Elevator Lobby has exit access into the Peds unit and the Peds unit has exit access to the Elevator Lobby. The Elevator Lobby otherwise has access to at least one exit into the Atrium Building to comply with 7.4.1.6.1. The doors marked as exit access are locked without use of Delayed Egress in compliance with 7.2.1.6.1 as permitted by 19.2.2.2.4(2). The doors are otherwise not in full compliance with 19.2.2.2.5.2(2) because a remote release from the Peds side is not provided from within the locked space.
D. On 4/16/19 at 11:25 AM, while in the company of the DMCE, it was observed that a magnetic locking device was installed on the Business occupancy 7th floor Stair "D" door. The magnets were not active at the time of the inspection but permanent disablement could not be confirmed because components which could become functional appeared to be installed. The doors were not provided with the required signage to comply with 7.2.1.6.1.1(4) in accordance with Delayed Egress locking devices as permitted by 39.2.2.2.5 or sensors and manual release buttons to comply with 7.2.1.6.2(1) & (3) in accordance with Access Controlled Egress systems as permitted by 39.2.2.2.6.
E. On 4/16/19 at 1:40 PM, while in the company of the DMCE, it was observed that a magnetic locking device was installed on the 6th floor Peds Stair "A" door which becomes locked only by the child abduction locking system. The ability to remotely release the lock was indicated not to be provided in accordance with 19.2.2.2.5.2(2) when the door may be locked by the abduction system. Any activation (including by manual pull station) of the fire alarm system was indicated to release the locks, but only activation by sprinkler flow or smoke detection in accordance with 19.2.2.2.5.2(5) is required for the fire alarm system to release the locks.
F. On 4/16/19 at 2:15 PM, while in the company of the DMCE, it was observed that Exit signage is provided to indicate the doors equipped with magnetic locking devices at the cross corridor doors of the 5th floor Kellogg Node are an exit access from the Elevator Lobby into the ED Overflow unit. The Elevator Lobby otherwise has access to at least one other exit into the Atrium Building to comply with 7.4.1.6.1. The doors marked as exit access are locked without use of Delayed Egress in compliance with 7.2.1.6.1 as would be permitted by 19.2.2.2.4(2).
G. On 4/16/19 at 2:35 PM, while in the company of the DMCE, it was observed that the cross corridor doors at the west side of the 5th floor were equipped with magnetic locking devices which provide access to Stair "A". The magnets were not active at the time of the inspection but permanent disablement could not be confirmed because components which could become functional appeared to be installed. The doors were not provided with the required signage to comply with 7.2.1.6.1.1(4) in accordance with Delayed Egress locking devices as permitted by 39.2.2.2.5 or sensors to comply with 7.2.1.6.2(1) in accordance with Access Controlled Egress systems as permitted by 39.2.2.2.6. The doors are otherwise not in full compliance with 19.2.2.2.5.2(2) because a remote release from the ED Overflow side is not provided from within the locked space.
H. On 4/17/19 at 10:35 AM, while in the company of the DMCE, it was observed that magnetic locking devices were installed at the exterior exit doors at the Old North Entry to grade. The installation was provided with the manual release button but lacked the sensor to comply with 7.2.1.6.2(1) as an Access-Controlled Egress door installation.
Tag No.: K0225
Based on observation, not all stairs or smokeproof enclosures are constructed and maintained as required. This deficient practice could affect patients, staff, and visitors in the building because their egress from the building could be impeded if the stairs and smokeproof enclosures are not properly constructed and maintained.
Findings include:
A. On 4/16/19 at 10:30 AM, while in the company of the DMCE, it was observed within the Stair "C" enclosure that electrical systems not serving the stair at the 13th & 14th level were identified as serving exterior building signage which does not comply with 7.1.3.2.1(10).
B. On 4/17/19 at 11:05 AM, while in the company of the DMCE, it was observed that the IT Closet at the 1st floor exit passageway at the discharge level of Stair "C" was provided with one door which was only a 20 minute door in lieu of the 90 minute door required by 7.1.3.2.1(9)(c).
Tag No.: K0251
Based on observation, not all egress paths lead to an exit. This deficient practice could require a person to traverse a longer route to reach an exit. This deficient practice may compromise the prompt care and movement of patients, visitors and staff during a fire/smoke emergency.
Finding includes:
On 4/17/19 at 1:15 PM while accompanied by the PM, corridors were observed which lack designated access to two remote exits and therefore produce dead end conditions which does not comply with 19.2.5.9 and 19.2.5.10.
Location observed: Corridor AP-500C10 North exit leads into the PACU suite.
Tag No.: K0254
Based on observation, not all habitable rooms are provided with direct access to a corridor or to the outside as required. This deficient practice could affect patients, staff, and visitors in those rooms because their egress from the building could be impeded if access to a corridor or to the outside is not provided.
Findings include:
On 4/16/19, while accompanied by the VPF, observation determined that egress paths require building occupants to pass through hazardous areas, as prohibited by 7.5.2.1, because those portions of the indicated building story are under construction and contain combustible materials. Locations observed include:
A. At 10:32 AM: 8th Floor egress path from Center Elevator Lobby to South Exit Stair.
B. At 10:33 AM: 8th Floor egress path from Center Elevator Lobby to North Exit Stair.
Tag No.: K0281
Based on observation and staff interview, illumination of the exit discharge portion of the means of egress is not provided to maintain illumination of the means of egress in the event of failure of the normal power supply. Failure to maintain illumination of the means of egress can affect all persons in the facility required to utilize the exit(s) by preventing safe and unimpeded access to the public way.
Findings include:
A. On 4/17/19, while in the company of the DMCE, it was observed that typical exit discharge lighting was not of the instant-on type to provide illumination within the required 10 second period to comply with 19.2.8, 19.2.9 and 7.8 & 7.9.1.3. Locations include:
1. At 11:10 AM at the Exit discharge locations for the 1st floor Administration suite and Stair "C".
2. At 11:15 AM at the Exit discharge exterior stair & path from the Basement level Com Ed Vault area to the south.
Tag No.: K0293
Based on observations and staff interview, exit signs are not displayed to define access to at least two means of egress from a floor level to comply with code requirements. Failure to define access to exits can prevent occupants from reaching an alternate exit when the primary exit access is comprised.
Findings includes:
A. On 4/16/19 while in the company of ITDCP, following are the locations not in accordance with Section 7.10.1.8:
1. At 1:30 PM at the 13th floor East side
2. At 1:55 PM at the 12th floor middle patient area near service door
3. At 2:25 PM at th 10th southeast dead end corridor
4. At 2:50 PM at the 8th floor:
a) At Southeast stairwell exit
b) At corridor to Atrium building
c) At the Exterior exit corridor to NICU/Delivery
B. On 4/17/19 while in the company of ITDCP, following are the locations not in accordance with Section 7.10.1.8:
1. At 9:30 AM at the 9th floor north-south corridor
2. At 9:45 AM at the 7th floor east end southeast stair 'C' to PACU
3. At 10:15 AM at the 5th floor east cross corridor
4. At 11:25 AM at the 3rd floor far east north-south exit corridor at double door
Tag No.: K0311
Based on observation, not all vertical openings in the building are protected as required. This deficient practice could affect patients, staff, and visitors in the building because smoke and fire could pass between building stories if vertical openings are not protected.
Findings include:
On 4/16/19 at 10:02 AM, while accompanied by the VPF, a steel access panel in the floor of the Penthouse was observed to lack a minimum 1-1/2 hour fire rating required by Table 8.3.4.2.
Tag No.: K0321
Based on observation and staff interview hazardous area are not protected in accordance with code requirements. Failure to provide protection of areas with highest degree of hazard than normal to the remaining occupancy can compromise the safety of all occupants during a fire/smoke event originating within the hazardous area.
Finding includes:
On 4/17/19 at 9:45 AM it was observed while in the company of ITDCP, at the 9th floor large mechanical room that a bend in the door created a gap at the meeting stiles of the doors that was not in accordance with 19.3.2.1, 8.7.1.2, 8.4.3.5 and NFPA 80-2010, 6.1,4.
Tag No.: K0341
Based on observation the facility failed to provide complete smoke detection. This deficient practice could result in the delayed notification of fire/smoke which may affect patients, staff and visitors.
Findings include:
A. On 4/16-17/19 while in the company of ITDCP, the following smoke detectors were found located less than the required distance of 3'-0" from HVAC diffuser, not in accordance with Section 9.6, NFPA 70 and NFPA 72-2010 Edition, Section 17.7.3.1. Location includes:
1. On 4/16/19 at 1:59 PM at the 12th floor look-out point.
2. On 4/17/19 at 2:00 PM at the 3rd floor - Both sides of the double egress door # ETO3FASD69.
14416
Based on observation during the survey walk through the facility failed to provide protection for the fire alarm components. This deficient practice could affect patients, staff and visitors during a fire event.
The finding is:
B. On 4/17/19 at 1:50 PM accompanied by the PM, in the 15th floor Mechanical Room (ET-15002), it was observed that the fire alarm Notification Appliance Circuit (NAC) panel located in the North West corner was not provided with smoke detection as require by NFPA 72, 2010, 10.15.
Tag No.: K0344
Based on observation, not all fire alarm control functions are installed or operate as required. This deficient practice could affect patients, staff, and visitors in the building because the fire alarm system could fail to operate if its controls are not installed and do not function as required.
Findings include:
A. On 4/16/19, while accompanied by the VPF, observation determined that the following conditions exist in 7th Floor Electrical Closet at Electrical Panel E1-E7A Circuit 20, which serves a fire alarm system NAC Panel:
1. At 11:06 AM: The breaker is not labeled "FIRE ALARM" as required by NFPA 72 2010 10.5.2.2.
2. At 11:07 AM: The breaker is not provided with red marking as required by NFPA 72 2010 10.5.2.3.
B. On 4/16/19 at 11:06 AM, while accompanied by the VPF, observation determined that, in 7th Floor Oxygen Storage Room JB-700T, a fire alarm system NAC Panel is not labeled as to the Electrical Panel and Circuit which feeds it as required by NFPA 72 2010 10.6.5.2.1.
Tag No.: K0351
Based on staff interview the facility failed to install a complete building fire suppression system. This deficient practice could result in the delayed response and suppression during a fire event, which may affect patients, staff and visitors.
Findings include:
A. On 4/17/19 at 10:30 AM while in the company of ITDCP, it was observed that the large storage room in the sub-basement adjacent to the pharmacy and gift shop did not have a ceiling or full height wall to separate this space from the above ceiling area of the adjacent pharmacy and gift shop to provide containment of the space to provide effective activation of the sprinkler system to comply with NFPA 13-201-0,4.1 & 3.3.6
14416
B. On 4/15/19 at 2:00 PM during document review in the company of the MCE the surveyor identified by staff interview the lack of fire sprinkler protection for all of the building's traction elevator machine rooms. NFPA 13, 2010, 8.1.1
20224
C. On 04/17/2019 at 2:12 PM while in the company of the PM, the 5th floor Operating Room Sterile Core has numerous soffited wall locations containing combustible materials. The current sprinkler layout has a limited distribution and does not comply with NFPA 13 2010, 8.10.6.3 concerning obstructions.
Tag No.: K0353
Based on observation, the facility failed to inspect, test, and maintain its automatic sprinkler system as required. This deficient practice could affect patients, staff, and visitors in the hospital because the automatic sprinkler system could fail to operate under emergency conditions if it is not properly inspected, tested, and maintained.
Findings include:
On 4/16/19 at 11:09 AM, while accompanied by the VPF, observation determined that, in 7th Floor Patient Sleeping Room JB-707, a sprinkler head is coated with dust as prohibited by NFPA 25 2011 5.2.1.1.2(5).
Tag No.: K0361
Based on observations and staff interview, spaces open to the exit access corridor are not provided with protective features in accordance with Code requirements. Failure to provide protective features can compromise the use of the corridor when prompt notification of a fire/smoke event occurring within the space open to the exit corridor is not provided.
Findings include:
On 4/16/19 at 2:30 PM while in the company of ITDCP, 8th floor Conference room "A" was not provided with smoke detection to comply with Section 19.3.6.1 (2)(b).
Tag No.: K0363
Based on observation, not all corridor doors are installed and maintained as required. This deficient practice could affect patients, staff, and visitors in the area because smoke or fire could move from the separated rooms to the corridor doors are not properly installed and maintained.
Findings include:
On 4/16/19, while accompanied by the VPF, observation determined that the following deficiencies exist at the 4th Floor Conference Room JB-405 Dutch door:
A. At 2:02 PM: Both leafs are not positive latching, including the latching of the upper leaf into the lower leaf, as required by 19.3.6.3.13(1), because a manual throw-bolt is provided from the upper leaf to the lower leaf.
B. At 2:03 PM: The door lacks a rabbet, astragal, or bevel at the meeting edge as required by 19.3.6.3.13(2).
Tag No.: K0521
Based on observation, the facility failed to install the ventilation system in the required manner. The deficient practice could affect patients, staff and visitors in the hospital because smoke and fire could be permitted to move between building stories and fire compartments if the system is not properly installed.
Findings include:
On 4/17/19 at 11:15 AM while in the company of ITDCP, four fire dampers penetrating the two hour fire rated wall at the 4th floor east exit corridor were not installed with retaining angles, exposing an opening between the wall and fire damper, not in accordance with Sections 8.3.5.7 and NFPA 90A-2012, 5.4.7.
Tag No.: K0531
Based upon observation, elevators are not installed and maintained in accordance with Code requirements for Firefighter's Service. Failure to maintain Firefighter's Service can delay availability of the elevators for Firefighter's use during a fire event.
Findings include:
On 4/17/19 at 8:50 AM, while in the company of the DMCE, it was observed that the west public elevator lobby on the 3rd floor has a coffered ceiling in which total bay depth exceeds 12". The north bay lacks smoke detection to comply with NFPA 72-2010, 21.3.5 exception and 17.7.3.2.1.
Tag No.: K0541
Based upon observation, Rubbish/Laundry Chutes are not maintained in accordance with Code requirements. Failure to maintain chutes can provide a vertical path for fire and smoke to move to other floors of the building and compromise the safety of other occupants during a fire/smoke emergency.
Findings include:
A. On 4/16/19 at 11:45 AM, while in the company of the DMCE, it was observed that the chute access door of the Rubbish chute on the 8th floor was not self-closing to a latched condition to comply with 19.5.4.1.
B. On 4/16/19 at 2:30 PM, while in the company of the DMCE, it was observed that the chute access door on the 5th floor was not self-closing to a latched condition to comply with 19.5.4.1.
C. On 4/17/19 at 9:30 AM, while in the company of the DMCE, it was observed that the chute access door of the Rubbish chute on the 2nd floor was not self-closing to a latched condition to comply with 19.5.4.1.
D. On 4/17/19 at 11:15 AM, while in the company of the DMCE, it was observed that the Rubbish chute discharge room door at the Basement level was not self-closing to a latched condition to comply with 19.5.4.4 because it rubs on the floor and the latching mechanism is defeated by staff because they don't have a key to the locking door.
E. On 4/17/19 at 1:00 PM, while in the company of the DMCE, it was observed that the 2-hour rated south wing chute discharge room at the Basement level contained ventilation ducts which were not provided with fire dampers to comply with 8.3.5.
Tag No.: K0911
Based on observation, not all basic electrical components are installed and maintained as required. This deficient practice could affect patients, staff, and visitors in the building because the electrical system could fail to operate properly when needed if the electrical components are not properly installed and maintained.
Findings include:
A. On 4/16/19 at 1:42 PM, while accompanied by the VPF, observation determined that, in 5th Floor Electrical Closet JB-55E, Electrical Panel E2C5A, which is designated as being part of the Critical branch of the building's Type 1 Essential Electrical System, serves emergency lights, required by NFPA 99 2012 6.4.2.2.3.2(1) and NFPA 70 2011 517.32(A) to be served by the Life Safety Branch of that system.
B. On 4/16/19 at 1:48 PM, while accompanied by the VPF, observation determined that the door to the 1st Floor Electrical Switchgear Room lacks an out-swinging door with panic hardware required by NFPA 70 2011 450.43(C).
C. On 4/16/19 at 1:52 PM, while accompanied by the VPF, observation determined that, in the 1st Floor Electrical Closet the electrical panel is not provided with accurate panel directory as required by NFPA 70 2011 408-4(A).
Tag No.: K0912
Based on observation, not all electrical receptacles are installed and maintained as required. This deficient practice could affect patients, staff, and visitors in the rooms because electrical equipment required for their care may fail to operate under emergency conditions if the electrical receptacles are not properly installed and maintained.
Finding includes:
On 4/17/19 at 11:15 AM while accompanied by the PM., the surveyor's observation determined that critical care patient beds lack electrical receptacles served by normal power as required by NFPA 70 2011 517-19(A).
1. The location observed: Fifth floor Operating Room # 8.