Tag No.: K0051

Based on visual observation the facility failed to provide a fire alarm system with devices or equipment installed according to NFPA 72. The fire alarm system gives a sense of security to offer an advance warning in fire and/or smoke emergency. This deficient practice could potentially affect 40 of 40 residents.

Findings:

During the facility tour on 11/15/2011 at 3:00 pm, it was observed that the fire alarm horns/strobes on the first floor did not activate when the fire alarm system was tested. Without audible and visual devices, connected to the fire alarm system, the ones occupying the first floor of the building would not be aware of any possible danger.

The documentation provided by the fire alarm contractor on 10/24/11 indicated that the above devices were not functioning and the system was yellow tagged, indicating that an impairment was present. When interviewed, the adminstrator and maintenance personnel admitted to knowing that the problem existed

At 3:00pm, the facility was placed in Immediate Jeopardy for the fire alarm system horns/strobes not functioning on the first floor.

The Immediate Jeopardy was lifted at 5:45pm when the fireman, who was provided by the Houma Fire Department, arrived to implement the fire watch procedures.