HospitalInspections.org

Bringing transparency to federal inspections

4225 WOODS PLACE

ABILENE, TX null

No Description Available

Tag No.: K0029

Facility failed to fully protect all areas in accordance with the 2000 edition of the Life Safety Code, NFPA (National Fire Protection Association) 101. Findings included the following:

Surveyor observed between 11:00 and 11:30 am on 4/11/13 that Room 105, in admissions bldg was not sprinklered.

No Description Available

Tag No.: K0130

Facility did not assure that all biomedical equipment are inspected in accordance with the Standard for Health Care Facilities, NFPA 99. Findings included the following:

Surveyor observed on 4/11/13 between 11:00 and 11:30 am that 2 of 2 defribrolators were inspected annually. This does not meet NFPA 99, 7-6.3.1.2, 7-6.3.1.3 and 7-6.2.1.2 for testing intervals. Critical equipment shall be tested semi-annually.

No Description Available

Tag No.: K0147

Facility failed to keep electrical equipment in accordance with National Electrical Code, NFPA 70. Findings included the following:

Surveyor observed between 10 and 10:30am on 4/1/13 that a J-box was left open in the Mechanical Room above the Fire Alarm Control Panel.