Based on observations during the survey walk of the facility on the afternoon of 1/10/2013, while being accompanied by the Director of Quality, the facility failed to maintain the integrity of the corridors. Positive latching hardware was not provided at the isolation patient room ' s corridor door.
Tag No.: K0106
Based on review of records during the survey of facility on the afternoon of 1/10/2013, while being accompanied by the Director of Quality, the facility failed to provide documentation that the grounding system at inpatient care areas is being tested as follows: receptacle testing in patient care areas should be at least annually. Currently there are no critical care areas. Facility must initiate a log to retain these records.
Based on observations during the survey walk of the facility on the afternoon of 1/10/2013, while being accompanied by the Director of Quality, the facility failed to properly identify emergency electrical panels. The emergency electrical panels (EES) shall be readily identifiable as a component of the essential electrical system and shall be labeled "LIFE SAFETY", "CRITICAL", or "EQUIPMENT" as applicable.