Bringing transparency to federal inspections
Tag No.: K0012
The facility failed to provide the correct building type per code. Findings include:
During the survey, the following is an example of what was observed:
The main entrance has an approximately 14' x 8' combustible covered area, observed not to have sprinkler coverage.
2000 NFPA 101, 19.1.6.2 Health care occupancies shall be limited to the types of building construction shown in Table 19.1.6.2. (See 8.2.1.)
Table 19.1.6.2 Construction Type Limitations
Construction Stories
Type
1 2 3 4 or
More
I(443) X X X X
I(332) X X X X
II(222) X X X X
II(111) X X* X* NP
II(000) X* X* NP NP
III(211) X* X* NP NP
III(200) X* NP NP NP
IV(2HH) X* X* NP NP
V(111) X* X* NP NP
V(000) X* NP NP NP
X: Permitted type of construction.
NP: Not permitted.
*Building requires automatic sprinkler protection. (See 19.3.5.1.)
.
Tag No.: K0017
The facility failed to provide corridor walls that would provide at least a 30 minute fire resistance rating. Findings include: During the survey, the following are examples of what was observed:
1. Unsealed penetrations at the end of three sleeve's in the coridor wall, by the ADON Office.
2. Coridor wall not sealed at the deck, this surveyor observed four differ areas, in differ locations of the wall.
NFPA 101, 19.3.6.1 Corridors in unsprinklered smoke compartments shall be separated from all other areas by partitions having a fire resistance rating of at least 30 minutes.
Tag No.: K0056
Sprinkler coverage was observed during the survey not adequately provided. Findings include: During the survey, the following are examples of what was observed:
Corrosion build up on a sprinkler in the Dishwashing Room.
1999 NFPA 25, 2-2.1.1 and 2-4.1.2 Sprinklers that are painted, corroded or damaged shall be replaced with new listed sprinklers of the same characteristics, including orifice size, thermal response, and water distribution.
Tag No.: K0062
The facility failed to comply with the required maintenance of the facility sprinkler system. During the survey, the following are examples of what was observed:
The Fire Department Connection was obstructed by a bush, and identification sign was not provided.
NFPA 101,2000 Edition, 9.7.5 Maintenance and Testing. All automatic sprinkler and standpipe systems required by this code shall be inspected, tested, and maintained in accordance with NFPA 25, Standards for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems.
NFPA 25, 1998 Edition, 9-7.1 Fire department connections shall be inspected quarterly. The inspection shall verify the following:
(a) The fire department connections are visible and accessible.
(b) Couplings or swivels are not damaged and rotate smoothly.
(c) Plugs or caps are in place and undamaged.
(d) Gaskets are in place and in good conition.
(e) Identification signs are in place.
(f) The check valve is not leaking.
(g) The automatic drain valve is in place and operating properly.
Tag No.: K0070
The facility failed to prohibit portable space heating devices. Findings include:
During the survey, the following is an example of what was observed:
A portable space heating device was observed in the Drs' Lounge.
2000 NFPA 101, 19.7.8 Portable space-heating devices shall be prohibited in all health care occupancies. Exception: Portable space-heating devices shall be permitted to be used in nonsleeping staff and employee areas where the heating elements of such devices do not exceed 212?F (100?C).
.