HospitalInspections.org

Bringing transparency to federal inspections

4455 DUNCAN AVE

SAINT LOUIS, MO null

Sprinkler System - Maintenance and Testing

Tag No.: K0353

Based on staff interview and record review, facility staff failed to inspect one of one wet sprinkler systems per NFPA 25, Standard for the Inspection, Testing, and maintenance of Water-Based Fire Protection Systems, 2011 edition. The facility census was 20.

Record review on 05/31/2018 did not show the following inspections:

-five (5) year check valve internal inspection

-five (5) year gauge calibration/replacement

-five (5) year internal pipe inspections/testing

During an interview on 5/31/18 at 11:22 A.M., the Facilities Manager confirmed the observations.

Refer to NFPA 25, Standard for the Inspection, Testing, and maintenance of Water-Based Fire Protection Systems, 2011 edition, Chapters 5, 13 and 14 for additional information.

5.3.2* Gauges.

5.3.2.1 Gauges shall be replaced every 5 years or tested every
5 years by comparison with a calibrated gauge.

5.3.2.2 Gauges not accurate to within 3 percent of the full
scale shall be recalibrated or replaced.

13.4.2 Check Valves.

13.4.2.1 Inspection. Valves shall be inspected internally every
5 years to verify that all components operate correctly, move
freely, and are in good condition.

14.2 Internal Inspection of Piping.

14.2.1 Except as discussed in 14.2.1.1 and 14.2.1.4 an inspection
of piping and branch line conditions shall be conducted
every 5 years by opening a flushing connection at the end of
one main and by removing a sprinkler toward the end of one
branch line for the purpose of inspecting for the presence of
foreign organic and inorganic material.

Maintenance, Inspection and Testing - Doors

Tag No.: K0761

Based on facility staff interview and record review, facility staff failed to inspect, test and maintain the fire egress doors in accordance with the 2010 Editions of NFPA 80 (Standard for Fire Doors and Other Opening Protectives) and NFPA 105 (Standard for Fire Doors and Other Opening Protectives). Facility staff failed to conduct an annual inspection of the non rated doors in the building. The facility census was 20.

1. Review of the facility's inspection, testing and maintenance records did not show documentation of an annual inspection of the fire egress doors and non rated doors in the building.

During an interview on 5/31/18 at 11:22 A.M., the Facilities Manager confirmed the observations.

NFPA 101, 2012 Edition states:

19.2.2.2.1 Doors complying with 7.2.1 shall be permitted.

7.2.1.15 Inspection of Door Openings.

7.2.1.15.1* Where required by Chapters 11 through 43, the
following door assemblies shall be inspected and tested not
less than annually in accordance with 7.2.1.15.2 through
7.2.1.15.8:
(1) Door leaves equipped with panic hardware or fire exit
hardware in accordance with 7.2.1.7
(2) Door assemblies in exit enclosures
(3) Electrically controlled egress doors
(4) Door assemblies with special locking arrangements subject
to 7.2.1.6

7.2.1.15.2 Fire-rated door assemblies shall be inspected and
tested in accordance with NFPA 80, Standard for Fire Doors and
Other Opening Protectives. Smoke door assemblies shall be inspected
and tested in accordance with NFPA 105, Standard for
Smoke Door Assemblies and Other Opening Protectives.

7.2.1.15.3 The inspection and testing interval for fire-rated
and nonrated door assemblies shall be permitted to exceed 12
months under a written performance-based program in accordance
with 5.2.2 of NFPA 80, Standard for Fire Doors and Other
Opening Protectives.

7.2.1.15.4 A written record of the inspections and testing
shall be signed and kept for inspection by the authority having
jurisdiction.

7.2.1.15.5 Functional testing of door assemblies shall be performed
by individuals who can demonstrate knowledge and
understanding of the operating components of the type of
door being subjected to testing.

7.2.1.15.6 Door assemblies shall be visually inspected from
both sides of the opening to assess the overall condition of the
assembly.

7.2.1.15.7 As a minimum, the following items shall be verified:
(1) Floor space on both sides of the openings is clear of obstructions,
and door leaves open fully and close freely.
(2) Forces required to set door leaves in motion and move to
the fully open position do not exceed the requirements
in 7.2.1.4.5.
(3) Latching and locking devices comply with 7.2.1.5.
(4) Releasing hardware devices are installed in accordance
with 7.2.1.5.10.1.
(5) Door leaves of paired openings are installed in accordance
with 7.2.1.5.11.
(6) Door closers are adjusted properly to control the closing
speed of door leaves in accordance with accessibility requirements.
(7) Projection of door leaves into the path of egress does not
exceed the encroachment permitted by 7.2.1.4.3.
(8) Powered door openings operate in accordance with
7.2.1.9.
(9) Signage required by 7.2.1.4.1(3), 7.2.1.5.5, 7.2.1.6, and
7.2.1.9 is intact and legible.
(10) Door openings with special locking arrangements function
in accordance with 7.2.1.6
(11) Security devices that impede egress are not installed on
openings, as required by 7.2.1.5.12.

Fundamentals - Building System Categories

Tag No.: K0901

Based on record review and facility staff interview, the facility failed to ensure that all building systems had been assigned a risk assessment category and documented. The census was 20.

1. Review of the facility documents for fire safety, building system tests, and policies did not show categorical risk assessments for the building systems.

2. During an interview on 5/31/18 at 11:23 A.M., the Facilities Manager said the risk assessments are in process and inventory is being completed.

The National Fire Protection Association 99 Health Care Facilities Code, 2012 edition, Chapter 4 states:

"Chapter 4 Fundamentals

4.1* Building System Categories. Building systems in health
care facilities shall be designed to meet system Category 1
through Category 4 requirements as detailed in this code.

4.1.1* Category 1. Facility systems in which failure of such equipment
or system is likely to cause major injury or death of patients
or caregivers shall be designed to meet system Category 1 requirements
as defined in this code.

4.1.2* Category 2. Facility systems in which failure of such equipment
is likely to cause minor injury to patients or caregivers shall
be designed to meet system Category 2 requirements as defined
in this code.

4.1.3 Category 3. Facility systems in which failure of such equipment
is not likely to cause injury to patients or caregivers, but can
cause patient discomfort, shall be designed to meet system Category
3 requirements as defined in this code.

4.1.4 Category 4. Facility systems in which failure of such equipment
would have no impact on patient care shall be designed to
meet system Category 4 requirements as defined in this code.

4.2* Risk Assessment. Categories shall be determined by following
and documenting a defined risk assessment procedure.

4.3 Application. The Category definitions in Chapter 4 shall
apply to Chapters 5 through 11."