Bringing transparency to federal inspections
Tag No.: K0025
Based on observations, on January 13, 2013 at approximately 9:30am onward, the one hour smoke barrier is incomplete. Barrier doesn't extend from outside wall to outside wall, and from floor to underside of floor slab above.
42 CFR 482.41(a)
Tag No.: K0029
Based on observations, on January 13, 2013 at approximately 9:30am onward, the fire door to material supply room is held-open by a storage rack behind door. Room is identified as number 6302.
42 CFR 482.41(a)
Tag No.: K0051
Based on observations, on January 13, 2013 at approximately 9:30am onward, the circuit number and panelboard serving normal power to the fire alarm control panel is not labeled on panel.
42 CFR 482.41(a)
Tag No.: K0076
Based on observations, on January 13, 2013 at approximately 9:30am onward, there are combustibles within five feet of oxygen cylinders. Cylinders are located in room 6302 material supply area.
42 CFR 482.41(a)
Tag No.: K0106
Based on observations, on January 13, 2013 at approximately 9:30am onward, the generator annunciator panels are located within an unsupervised room in the steam plant. The room was unattended at the time of survey; audible signals generated on the panel could not be heard over ambient sound levels surrounding area.
42 CFR 482.41(a)
Tag No.: K0147
Based on observations, on January 13, 2013 at approximately 9:30am onward, there is no lighting identified as connected to the normal power distribution panel for corridor serving room 6302. During survey, emergency lighting in the identified corridor was interrupted with no lighting remaining energized on normal power system.
42 CFR 482.41(a)