HospitalInspections.org

Bringing transparency to federal inspections

300 PARK HILL DRIVE

FREDERICKSBURG, VA null

No Description Available

Tag No.: K0018

Based on observations it was determined that the health care facility failed to maintain the correct operation of a patients hallway door. This has the possibility to affect 35% of the residents.

The Findings Include:
On 5/2/2013 at approximately 1450 hours, it was revealed by observation and interview that the door to room 305 would not close and latch.

An interview on 5/2/2013 at approximately 1450 hours with maintenance personnel confirmed this evidence.

No Description Available

Tag No.: K0052

Based on observations it was determined that the health care facility failed to maintain the proper ceiling integrity. This has the possibility to affect 35% of the residents.

The Findings Include:
On 5/2/2013 at approximately 1455 hours, it was revealed by observation and interview that multiple ceiling tiles were missing in the east data closet.

An interview on 5/2/2013 at approximately 1455 hours with maintenance personnel confirmed this evidence.

No Description Available

Tag No.: K0062

Based on observations it was determined that the health care facility failed to maintain fire protection components throughout the facility. This has the possibility to affect 100% of the residents.

The Findings Include:
On 5/2/2012 at approximately 1400 hours, it was revealed by observation and interview that the nozzle placement for the kitchen appliances under the hood was not correct.

On 5/2/2013 between 1330 hours and 1515 hours, it was revealed by observation and interview that a there was dust build up on sprinkler heads throughout the facility.

An interview on 5/2/2013 at approximately 1515 hours with maintenance personal confirmed this evidence.

No Description Available

Tag No.: K0067

Based on observations it was determined that the health care facility failed to maintain the excessive build up of dust and combustible storage. This has the possibility to affect 75% of the residents.

The Findings Include:
On 5/2/2013 at approximately 1330 hours, it was revealed by observation and interview that there were combustibles in the boiler room.

On 5/2/2013 at approximately 1500 hours, it was revealed by observation and interview that there were combustibles in the east electrical room.

On 5/2/2013 at between 1330 and 1515 hours, it was revealed by observation and interview that there was excessive dust build up on vents and returns throughout the facility.

An interview on 5/2/2013 at approximately 1515 hours with maintenance personnel confirmed this evidence.

No Description Available

Tag No.: K0130

Based on observations it was determined that the health care facility failed to properly secure a compressed gas cylinder.

The Findings Include:

On 5/2/2013 it was revealed by observation and interview that the compressed gas cylinder for the soda fountain was not properly secured. Statewide Fire Prevention Code section 3003.5.3 requires the proper securing of compressed gas cylinders from falling over.

An interview on 5/2/2013 with maintenance personal confirmed this evidence.

Means of Egress - General

Tag No.: K0211

Based on observations it was determined that the health care facility failed to maintain the required spacing between alcohol based hand rub dispensers and an ignition source. This has the possibility to affect 35% of the residents.

The Findings Include:
On 5/2/2013 at approximately 1430 hours, it was revealed by observation and interview that there was an alcohol based hand rub dispenser mounted directly over a light in patient room 118.

An interview on 5/2/2013 at approximately 1430 hours with maintenance personnel confirmed this evidence.