2311 N OREGON STREET

EL PASO, TX null

Means of Egress Requirements - Other

Tag No.: K0200

K200 Inspection of Doors in Means of Egress - Records

Findings:

The inspector observed, while accompanied by the Director of Plant Operations, during the hours of the inspection from 8:00 AM to 11:30 AM on 08/08/18, that there were the following issues:

1) Based on staff interview, the facility has not yet implemented inspection of doors in means of egress.

HVAC

Tag No.: K0521

K521 HVAC

Findings:

The inspector observed, while accompanied by the Director of Plant Operations, during the hours of the inspection from 8:00 AM to 11:30 AM on 08/08/18, that there were the following issues:

1) Based on staff interview, final filters, and filter frames were not visually inspected for pressure drop and for bypass on a consistent frequency interval.

Electrical Systems - Maintenance and Testing

Tag No.: K0914

K914 Electrical Systems - Maintenance and Testing

Findings:

The inspector observed, while accompanied by the Director of Plant Operations, during the hours of the inspection from 8:00 AM to 11:30 AM on 08/08/18, that there were the following issues:

1) There was no record to show that facility was conducting receptacle testing in patient care areas. Staff indicated that he was relatively a new hire and thus was unfamiliar where his predecessor kept the records. Hospital needs to develop better record management system in order to maintain continuity of service and deliver acceptable performance standards.