Tag No.: K0018
Based on observation on Tuesday, 1/26/2010 at approximately 11:00 AM onward:
Corridor doors to patient rooms 207 and 226 would not close /latch/seal without extra force. The isolation equipment racks hung over the door with hooks were impeding the closing of the doors.
Tag No.: K0038
Based on observation on Tuesday, 1/26/2010 at approximately 11:00 AM onward:
There were keyed deadbolt locks on corridor doors to patient rooms 220, 228 and to Pharmacy (1st floor). These locks were not found in use at time of survey.
Tag No.: K0052
Based on observation on Tuesday, 1/26/2010 at approximately 11:00 AM onward:
It was not noted at the main FACP nor remote annunciator panel which electrical panel box/circuit breaker served the FACP.
Tag No.: K0072
Based on observation on Tuesday, 1/26/2010 at approximately 11:00 AM onward:
There was excess equipment, charting tables on wheels, chairs , BP monitors, shredding table, etc located in the corridor left unattended /not in immediate use.
Tag No.: K0106
Based on observation on Tuesday, 1/26/2010 at approximately 11:00 AM onward:
The emergency generator alarm panel was not located at regularly manned station inside the facility.