Protection - Other

Tag No.: K0300

The inspector observed, while accompanied by the Facilities Manager during the hours of the inspection from 11:00 am to 4:30 pm on 2/7/2017 that there were the following issues.

Based on observation the facility failed to provide an escutcheon plate for the sprinkler head located at (2nd Floor: Facilities Wing: Equipment Storage Room)

Based on observation the facility failed to provide adequate clearance between a sprinkler head and stored items in the kitchen storage room. ''The clearance between the deflector and the top of storage shall be 18 inches or greater.'' - NFPA 13, 2010: 8.5.6.1.

Interior Wall and Ceiling Finish

Tag No.: K0331

The inspector observed, while accompanied by the Facilities Manager during the hours of the inspection from 11:00 am to 4:30 pm on 2/7/2017 that there were the following issues. Based on observation the facility failed to provide documentation showing that wall finishes, ceiling finishes and interior floor finishes meets Class A or Class B flame spread ratings.

Fire Alarm System - Installation

Tag No.: K0341

The inspector observed, while accompanied by the Facilities Manager during the hours of the inspection from 11:00 am to 4:30 pm on 2/7/2017 that there were the following issues. The gymnasium has an exterior exit with an emergency exit sign. Therefore this exit must have a fire alarm pull box. This pull box is missing.

Draperies, Curtains, and Loosely Hanging Fabr

Tag No.: K0751

The inspector observed, while accompanied by the Facilities Manager during the hours of the inspection from 11:00 am to 4:30 pm on 2/7/2017 that there were the following issues. Based on observation the facility failed to provide documentation showing that draperies, curtains and loosely hanging fabrics meet the requirements of 10.3.1 of NFPA-701.

Upholstered Furniture and Mattresses

Tag No.: K0752

The inspector observed, while accompanied by the Facilities Manager during the hours of the inspection from 11:00 am to 4:30 pm on 2/7/2017 that there were the following issues. Based on observation the facility failed to provide documentation showing that furniture and mattresses meet the requirements of 10.3.2.1 and 10.3.3 of NFPA-701.

Fundamentals - Building System Categories

Tag No.: K0901

The inspector observed, while accompanied by the Facilities Manager during the hours of the inspection from 11:00 am to 4:30 pm on 2/7/2017 that there were the following issues. Based on observation the facility failed to provide records of building systems that are designed to meet Category 1 through 4 requirements as detailed in NFPA 99. Categories are determined by a formal and documented risk assessment procedure performed by qualified personnel. Chapter 4 (NFPA 99)

Electrical Systems - Maintenance and Testing

Tag No.: K0914

The inspector observed, while accompanied by the Facilities Manager during the hours of the inspection from 11:00 am to 4:30 pm on 2/7/2017 that there were the following issues. Based on observation the facility failed to provide records of receptacle tests, repairs or modifications per the requirements in 6.3.4 of NFPA 99.

Hyperbaric Facilities

Tag No.: K0931

The inspector observed, while accompanied by the Facilities Manager during the hours of the inspection from 11:00 am to 4:30 pm on 2/7/2017 that there were the following issues. Based on observation the facility failed to provide records of fire drills in the hyperbaric facilities per 14.3.1.4.5 of NFPA 99.