HospitalInspections.org

Bringing transparency to federal inspections

2 SOUTH HOSPITAL DRIVE

MURPHYSBORO, IL 62966

No Description Available

Tag No.: K0029

Based on observation during the survey walk-through, not all hazardous areas are separated from the remainder of the building. These deficiencies could affect any patients, staff, or visitors in the building by allowing smoke or fire to pass into other occupied portions of the building.

Findings include:

On March 8, 2016, at 2:11 PM, while accompanied by the FEM, the surveyor observed a hold-open device, which does not comply with 19.3.2.1 and 8.2.3.2.3.1(2), on the door to the Surgery Department Store Room.

No Description Available

Tag No.: K0056

Based on observation during the survey walk-through, not all portions of the facility's automatic sprinkler system are properly installed and maintained. These deficiencies could affect any patients, staff, or visitors in the area of the conditions cited because the activation of sprinkler heads could be delayed.

Findings include:

While accompanied by the FEM, the surveyor observed rooms or spaces within designated sprinklered smoke compartments which lack sprinkler heads required by NFPA 13 1999 5-1.1.(1). Locations observed include (all Second Floor):

A. March 8, 2016, 12:51 PM: Southeast Exit Stair.

B. March 8, 2016, 12:55 PM: Sleep Study Unit Supply Room.
C. March 8, 2016, 1:03 PM: Center Convenience Stair.

D. March 8, 2016, 1:16 PM: West Exit Stair.

No Description Available

Tag No.: K0130

Based on observation during the survey walk-through, document review, and staff interview, the facility is not in compliance with a series of Life Safety and other code requirements that are not documented under other K-Tags.

Findings include:

Due to the number, variety, and severity of the life safety deficiencies observed during the survey walk-through, the provider shall institute appropriate interim life safety measures until all cited deficiencies are corrected. The provider shall include, as an attachment to its Plan of Correction (PoC) and referenced therein, a detailed narrative and proposed schedule for all such measures. The narrative shall describe all measures to be implemented, as well as the frequency with which they are to be conducted, and shall indicate the manner in which the measures are to be documented. The narrative shall also include comments related to changes in the interim life safety measures to remain in place as work toward the completion of its PoC progresses.