Tag No.: K0018

Based on observation the facility failed to provide doors that close, latch, or resist the passage of smoke as per National Fire Protection Association (NFPA) 101 (Life Safety Code). This deficiency affects all 45 patients in the facility.

Note: NFPA 101, 2000 edition
NFPA 101 Chapter 19, " Existing Health Care Occupancy, " 19.3.6.3.1 Doors protecting corridor openings in other than required enclosures of vertical openings, exits, or hazardous areas shall be substantial doors, such as those constructed of 1 3/4-in. thick, solid-bonded core wood or of construction that resists fire for not less than 20 minutes and shall be constructed to resist the passage of smoke. Compliance with NFPA 80, Standard for Fire Doors and Fire Windows, shall not be required.
And
Note: NFPA 101, 2000 edition
NFPA 101 Chapter 19, "Existing Health Care Occupancy, " 19.3.6.3.3 Hold-open devices that release when the door is pushed or pulled shall be permitted. Doors should not be blocked open by furniture, door stops, chocks, tie-backs, drop-down or plunger-type devices, or other devices that necessitate manual unlatching or releasing action to close. Examples of hold-open devices that release when the door is pushed or pulled are friction catches or magnetic catches.

Findings:

During facility tour on October 23, 2013 between 8:00 a.m. and 4:00 p.m. the door to the following rooms did not close, latch, or resist the passage of smoke.

1. The corridor door to rooms 206, 211, 228, 309, 312, 313, 325, 348, and 350 has gaps between the frame and the door. The gaps would allow smoke to move between the room and corridor.

When asked about the gaps between the doors and the frame the supervisor of Plant Operations stated that some the material that was placed on the doors to seal it was recently removed in order for the door frames to be painted.