3200 CENTER VALLEY PARKWAY

CENTER VALLEY, PA null

Building Construction Type and Height

Tag No.: K0161

Based on observation and interview, it was determined the facility failed to maintain building construction requirements, affecting four of four floors in this component.

Findings include:

1. Observation of building construction on October 5, 2021, between 12:00 p.m. and 1:00 p.m., revealed the component exceeded the maximum allowable story height for this type of construction.

Exit interview with the Facilities Director on October 6, 2021, between 10:45 a.m. and 11:00 a.m., confirmed the building construction deficiency.

Exit Signage

Tag No.: K0293

Based on observation and interview, it was determined the facility failed to install and maintain exit signage in one location, affecting one of four floors.

Findings include:

1. Observation on October 5, 2021, at 12:39 p.m., revealed the ground floor, Mechanical Room, lacked exit signage above the exit door.

Exit interview with the Facilities Director on October 6, 2021, between 10:45 a.m. and 11:00 a.m., confirmed the exit signage deficiency.

Corridor - Doors

Tag No.: K0363

Based on observation and interview, it was determined the facility failed to maintain corridor openings in four locations, affecting one of two floors.

Findings include:

1. Observation on October 6, 2021, between 9:22 a.m. and 9:45 a.m., revealed the following:

a. 9:22 a.m., the first floor, Dining Lounge door required adjustment to fully latch.
b. 9:33 a.m., the first floor, Janitor Closet door required adjustment to fully latch.
c. 9:40 a.m., the first floor, North Lounge door was not smoke-tight.
d. 9:45 a.m., the first floor, Patient Room 114 door was not smoke-tight.

Exit interview with the Facilities Director on October 6, 2021, between 10:45 a.m. and 11:00 a.m., confirmed the corridor opening deficiences.

Gas Equipment - Cylinder and Container Storag

Tag No.: K0923

Based on observation and interview, it was determined the facility failed to maintain cylinder storage in one location, affecting one of four floors.

Findings include:

1. Observation on October 5, 2021, at 12:22 p.m., revealed an unsecured oxygen cylinder, located within the Therapy Department.

Exit interview with the Facilities Director on October 6, 2021, between 10:45 a.m. and 11:00 a.m., confirmed the cylinder storage deficiency.