Bringing transparency to federal inspections
Tag No.: K0161
K161 BUILDING CONSTRUCTION TYPE AND HEIGHT 2012 EXISTING
Based on observation the facility failed to identify building construction type (Bungalow/one storey building.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that the building construction type could not be identified/determined and the building (patient care areas are not sprinklered.
Tag No.: K0200
Door Inspections:
Fire-rated door assemblies and certain other doors in the means of egress shall be tested annually or per an accepted performance-based evaluation schedule approved by the AHJ per NFPA 80, 2010, Ch. 5.2. A written record of the inspections and testing shall be signed and kept for inspection by the AHJ. NFPA101, 7.2.1.15.
Based on observation the facility failed to maintain properly all the doors along the means of egress.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that fire rated doors along the means of egress were not being inspected annually.
Tag No.: K0223
Based on observation the facility failed to maintain building protection.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that the storage areas are not 1-hour fire rated, the doors did not have closers and for an un-sprinklered building, the facility did not have adequate smoke detector protection in all the patient care rooms/areas and the education building included.
Tag No.: K0281
Illumination of means of egress, including exit discharge, is arranged in accordance with 7.8 and shall be either continuously in operation or capable of automatic operation without manual intervention. 18.2.8, 19.2.8
Illumination of Means of Egress.
7.8.1.4* Required illumination shall be arranged so that the failure of any single lighting unit does not result in an illumination level of less than 0.2 ft-candle (2.2 lux) in any designated area.
Based on observation the facility failed to provide adequate illumination at exit landing.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that in the exit landing were missing two points of lights.
Tag No.: K0500
Manual Fire Pull Station.
"Manual fire alarm boxes shall be located within 1.5m (5 feet) of exit doorway opening at each exit on each floor." NFPA 72, 2004, 5.12.6
Based on observation the facility failed to provide a manual fire pull 5ft to the door.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that at the emergency department main entrance door the manual fire pull station was more than 5 feet from the door.
Tag No.: K0902
Medical Bulk Storage clearance
"The minimum distance from any bulk oxygen system to any public sidewalk or parked vehicle shall be 10 ft." - NFPA 50, 2001, 2.2.12.
"The minimum distance from any bulk oxygen system to any line of adjoining property that can be built upon shall be 5 ft." - NFPA 50, 2001, 2.2.13.
"The minimum distance from any bulk oxygen system to any opening in walls of adjacent structures shall be 10 ft." - NFPA 50, 2001, 2.2.3
Based on observation, the facility failed to provide adequate clearance between the sidewalk or road bulk gas storage area.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022that the facility failed to provide adequate clearance between the sidewalk or vehicular roadway and the bulk medical gas storage area.
Tag No.: K0907
Based on observation the facility failed to provide a risk assessment for the medical gas system.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that the facility had not done a risk assessment to determine the procedures and schedule for testing the medical gas system.
Tag No.: K0911
Panel directory:
"Circuit Directory or Circuit Identification. Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be distinguished from all others. Spare positions that contain unused overcurrent devices or switches shall be described accordingly. The identification shall be included in a circuit directory that is located on the face or inside of the panel door in the case of a panelboard and located at each switch or circuit breaker in a switchboard. No circuit shall be described in a manner that depends on transient conditions of occupancy." - NFPA 70, 2011, 408.4 (A) Note: Labeling includes all disconnecting means, see 110.22.
Based on observation the facility failed to provide adequate Essential Electrical System (EES).
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that there were no Essential Electrical System (EES) in place hence, no panels nor directories.
Essential Electrical System Segregation (Life Safety):
"The essential electrical system shall be divided into the following three branches: (1) Life safety, (2) Critical, (3) Equipment." NFPA 99, 2012, 6.4.2.2.1.1.
6.4.2.2.3 Life Safety Branch.
6.4.2.2.3.1 The life safety branch shall be limited to circuits essential to life safety.
6.4.2.2.3.2 "The life safety branch shall supply power for lighting, receptacles, and equipment as follows:
(1) Illumination of means of egress in accordance with 101, Life Safety Code,
(2) Exit signs and exit directional signs in accordance with NFPA 101, Life Safety Code,
(3) Hospital communications systems, where used for issuing instruction during emergency conditions,
(4) Generator set locations as follows:
(a) Task illumination,
(b) Battery charger for emergency battery-powered lighting unit(s),
(c) Select receptacles at the generator set location and essential electrical system transfer switch locations,
(5) Elevator cab lighting, control, communications, and signal systems,
(6) Electrically powered doors used for building egress,
(7) Fire alarms and auxiliary functions of fire alarm combination systems complying with NFPA 72, National Fire Alarm and Signaling Code."
6.4.2.2.3.3 "Alarm and alerting systems (other than fire alarm systems) shall be connected to the life safety branch or critical branch."
6.4.2.2.3.4 "Loads dedicated to a specific generator, including the fuel transfer pump(s), ventilation fans, electrically operated louvers, controls, cooling system, and other generator accessories essential for generator operation, shall be connected to the life safety branch or the output terminals of the generator with overcurrent protective devices."
6.4.2.2.3.5 "No functions other than those in 6.4.2.2.3.2, 6.4.2.2.3.3, and 6.4.2.2.3.4 shall be connected to the life safety branch, except as specifically permitted in 6.4.2.2.3."
Based on observation the facility had incorrect circuits connected in the essential electrical system.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that there was no Essential Electrical System (EES) in the facility. Therefore there were no receptacles at Generator and ATS locations.
Essential Electrical System Segregation (Critical Branch)
"General Care Areas. Patient Bed Location. Each patient bed location shall be supplied by at least two branch circuits, one from the emergency system and one from the normal system all Branch circuits from the normal system shall originate in the same panelboard." NFPA 70, 2011, 517.18(A)
Patient Bed Location Receptacles. Each patient bed location shall be provided with a minimum of four receptacles. They shall be permitted to be of the single, duplex, or quadruplex type, or any combination of the three. All receptacles, whether four or more, shall be listed "hospital grade" and so identified. The grounding terminal of each receptacle shall be connected to an insulated copper equipment grounding conductor sized in accordance with Table 250.122.
Exception No. 1: The requirements of 517.18(B) shall not apply to psychiatric, substance abuse, and rehabilitation hospitals meeting the requirement of 517.18(B)(2).
Exception No. 2: Psychiatric security rooms shall not be required to have receptacle outlets installed in the room.
Informational Note: It is not intended that there be a total, immediate replacement of existing non-hospital grade receptacles. It is intended, however, that non-hospital grade receptacles be replaced with hospital grade receptacles upon modification of use, renovation, or as existing receptacles need replacement." NPFA 70, 2011, 517.18(B)
Based on observation the facility failed to provide lights from critical branch lights to all the patient care areas.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that all lights and receptacles at the patient care areas were on normal branch. Provide type I electrical system for the facility.
Generator EPOS or Kill Switch:
"All installations shall have a remote manual stop station of a type to prevent inadvertent or unintentional operation located outside the room housing the prime mover, where so installed, or elsewhere on the premises where the prime mover is located outside the building" - NFPA 110, 2010.
Based on observation the facility had incorrectly installed the Generator kill switch in a locked location.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that there was no generator kill switch installed outside the generator enclosure per the code.
Tag No.: K0913
Based on observation the facility failed to provide adequate risk assessment for all the operating rooms.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that risk assessments were not performed by the governing body to determine if the Operating rooms were wet or dry locations. If determined to be wet, they must be protected by line isolation monitors or GFCIs.
The facility Operating Room(s) have been decommissioned for about 3 years. The facility need state the intention of the hospital regarding the Operating room. This will determine the correct status of the Hospital. Currently, it is General Hospital without Operating room or Obstetrical unit, which is a wrong designation. As is the hospital need to be classified a Special Hospital per the state hospital Licensing Rule.
Tag No.: K0914
Based on observation the facility failed to provide adequate maintenance and testing of Essential Electrical System.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that there was no EES in the facility.
Tag No.: K0918
Based on observation the facility failed to provide adequate maintenance and testing of Essential Electrical System.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that there was no EES system.
Tag No.: K0924
Based on observation the facility failed to provide adequate medical gas equipment testing.
The inspector observed, while accompanied by the Quality Officer, Risk Management Officer, Operations/Safety Officer during the hours of the inspection from 10:00 am to 2:00 pm on 9/27/2022 that the facility had no scheduled maintenance program for medical gas equipment.