1975 BABCOCK RD

SAN ANTONIO, TX null

No Description Available

Tag No.: K0029

Based on observation the facility failed to provide adequate hazardous area separation.

The inspector observed, while accompanied by the Vice President of Facility Operations and the Security Officer during the hours of the inspection from 10:00 am to 12:15 pm on 5/14/2014 that there was the following issue. The soiled utility door at the " A " wing on the second floor did not close and latch properly.

No Description Available

Tag No.: K0034

Based on observation the facility failed to provide adequate stair enclosures.

The inspector observed, while accompanied by the Vice President of Facility Operations and the Security Officer during the hours of the inspection from 10:00 am to 12:15 pm on 5/14/2014 that the stairs were being used for storage of construction materials. The following stairs had storage inside of the enclosure, Stair " B " and " D " .

" There shall be no enclosed, usable space within an exit enclosure, including under stairs, nor shall any open space within the enclosure be used for any purpose that has the potential to interfere with egress. " NFPA 101, 2000, 7.2.2.5.3.

Means of Egress - General

Tag No.: K0211

Based on observation the facility failed to provide an acceptable location for alcohol based hand rub dispensers.

The inspector observed, while accompanied by the Vice President of Facility Operations and the Security Officer during the hours of the inspection from 10:00 am to 12:15 pm on 5/14/2014 that there were alcohol based hand rubs above or immediately adjacent to electrical switches in the nurse station on the first floor.