Tag No.: K0018
Facility failed to maintain corridor doors in accordance with the 2000 edition of the Life Safety Code, NFPA 101: Findings included the following:
Surveyor observed that 7 patient rooms and the staff lounge had roller latches on corridor doors.
Tag No.: K0069
Facility failed to maintain kitchen cooking equipment protection equipment in accordance with NFPA 10, Standard for Portable Fire Extinguishers. Findings included the following:
Survey observed between 1:30 and 2:30 pm on 1/07/14 that in kitchen, code required signage was missing. The placard shall read: fire protection system shall be activated prior to using the fire extinguisher [NPFA 10: 4.3.2.2].
Tag No.: K0076
Facility failed to maintain medical gas storage area in accordance with the Standard for Health Care Facilities, NFPA 99. Findings included the following:
Surveyor observed between 1:30 and 2:30pm on 1/07/14 that oxygen medical gas storage manifold was not protected from heating to a temperature of 130 degrees in accordance with NFPA 99: 4-3.1.1.2.