Tag No.: K0050

Based on record review, the facility failed to conduct quarterly fire drills as required.

Findings Include:

On December 4, 2014 at 10:00 a.m., during records review, it was observed that there were no recorded fire drills since February 2012. The maintenance person agreed with this observation.

No Description Available

Tag No.: K0052

Based on observation and testing, the facility failed to maintain the fire alarm system.

Findings Include:

On December 4, at 11:00 a.m., while testing the fire alarm system it was observed that the audible alarm in the senior care unit was not operable. The maintenance person agreed with this observation.

No Description Available

Tag No.: K0056

Based on observation, the facility failed to provide sprinkler protection throughout the facility.

Findings Include:

On December 4, 2014, at 10:35 a.m., it was observed that the toilet across from the nurses station was not protected with a sprinkler head. The maintenance person made this observation during the survey.

No Description Available

Tag No.: K0062

Based on record review and interview, the facility failed to conduct the annual sprinkler inspection.

Findings Include:

On December 4, 2014, at 10:00 a.m., during record review, it was observed that the sprinkler system was last inspected on July 12, 2012. The maintenance person agreed with this observation.

No Description Available

Tag No.: K0069

Based on record review and interview, the facility failed to conduct the required inspection on the kitchen hood extinguishing system.

Findings Include:

On December 4, 2014, at 10:45 a.m., it was observed that the last inspection on the kitchen hood extinguishing system was in July 2012. The maintenance person agreed with this observation.

No Description Available

Tag No.: K0144

Based on record review and interview, the facility failed to conduct the load test on the generator as required.

Findings Include:

On December 4, 2014, at 10:15 a.m., during record review, it was observed that the load test on the generator was conducted quarterly. The maintenance person stated that he thought it was required quarterly rather than monthly.