10648 PARK RD, 3RD FL

CHARLOTTE, NC null

No Description Available

Tag No.: K0018

Based on observation, on September 14, 2010 at approximately 1:00pm onward, the positive latching hardware did not function properly on door to resident room 7035. The door did not latch in the closed position.

No Description Available

Tag No.: K0033

Based on observation, on September 14, 2010 at approximately 1:00pm onward, the stairways in the following areas are incomplete:

a. exit passageway for northside stairway - is incomplete due to fire doors wedged in the open position.(kitchen exit discharge)

No Description Available

Tag No.: K0062

Based on observation, on September 14, 2010 at approximately 1:00pm onward, there are green bulb sprinklers provided in the storage room containing mechanical ducts - the heads are rated excessively above expected ambient temperatures in the occupied zone.(located on the eastside corridor nearest the southside of floor area)

No Description Available

Tag No.: K0072

Based on observation, on September 14, 2010 at approximately 1:00pm onward, there is unattended equipment stored in the exit corridor near east stairway.

No Description Available

Tag No.: K0106

Based on observation, on September 14, 2010 at approximately 1:00pm onward, the fire alarm control panel is wired to the normal power panelboard - panel 1F. The fire alarm panel must be wired to the Life Safety Branch of the essential electrical system.(located in the Security room)