Tag No.: K0018

Based upon observation and interview, it was determined the facility failed to maintain three corridor openings in three locations on two of six total floors.

Findings include:

1. Observation of various corridor openings between 11:02 a.m. and 11:33 a.m. on February 22, 2012, revealed the below deficiencies:

a. The third floor Multipurpose Room corridor entrance door is held open by unapproved means. 11:02 a.m.
b. The fourth floor Hair Wash Room corridor entrance door lacks smoke-tight integrity when coupled with the corresponding door frame assembly. 11:16 a.m.
C. The fourth floor GS 4001 corridor entrance door lacks smoke-tight integrity when coupled with the corresponding door frame assembly. 11:33 a.m.

Interview with facilities director at 11:35 a.m. on February 22, 2012, confirmed the corridor opening deficiencies.

No Description Available

Tag No.: K0038

Based upon observation and interview, it was determined the facility failed to maintain exit access in one location on one of six total floors.

Findings include:

Observation of the third floor exit access corridor located closest to stair tower one at 10:57 a.m. on February 22, 2012, revealed miscellaneous items located within the corridor.

Interview with facilities director at 10:58 a.m. on February 22, 2012, confirmed the items within the exit access corridor system.