Tag No.: K0039
Based on observation the facility failed to provide corridors that are clear and unobstructed for the complete width of the corridor for 1of 4 halls in the facility. This deficiency affects the 17 patients in the facility.
Note: NFPA 101, 2000 edition
NFPA 101:7.3. The width of means of egress shall be measured in the clear at the narrowest point of the exit component under consideration. Exception: Projections not more than 31/2 in. on each side shall be permitted at 38 in. and below.
Findings:
During facility tour on December 6, 2011 between 1:00 p.m. and 2:30 p.m. there were wheelchairs, scale, and pumps blocking the exit corridor by the main nurse station. Observations at 1:00p.m., 1:30p.m., 2:00p.m. and 2:30 p.m. revealed that these items were left unattended in the same locations for more than thirty minutes.
1. There were 5 wheelchairs on the left side of the exit corridor by the main nursing station.
2. There were 3 pump machines on the left side of the exit corridor by the main nursing station.
3. There was a scale on the left side of the exit corridor by the main nursing station.
Items left in the corridors would prevent the rapid removal of patients in case of a fire or disaster.