1401 MORRIS DRIVE

OKMULGEE, OK null

Subdivision of Building Spaces - Smoke Barrie

Tag No.: K0372

Based on observation and interview, the facility failed to maintain smoke barrier walls to provide at least a one half hour fire resistance rating. Findings:

1. A tour of the facility was conducted on 07/07/22, the two smoke walls located on 2 East had penetrations on both sides of the walls.