Bringing transparency to federal inspections
Tag No.: K0291
Based on observation and facility staff interview, facility staff failed to provide emergency lighting, without light switches, inside one of one medication rooms. The facility census was 20.
1. Observations on 2/28/18, during the Life Safety Code (LCS) tour, showed the light fixture in the medication room controlled by a light switch.
During an interview on 2/28/18 at 2:04 P.M., the Director/Team Leader confirmed the observation.
NFPA 101, 2012 edition, Section 7.9.2.7 states: "7.9.2.7 The emergency lighting system shall be either continuously in operation or shall be capable of repeated automatic
operation without manual intervention."
NFPA 99, 2012 edition, section 6.4.2.2.4.2 states:
"6.4.2.2.4.2 The critical branch shall supply power for task illumination,
fixed equipment, select receptacles, and select power
circuits serving the following areas and functions related to patient
care:
(1) Critical care areas that utilize anesthetizing gases, task illumination,
select receptacles, and fixed equipment
(2) Isolated power systems in special environments
(3) Task illumination and select receptacles in the following:
(a) Patient care rooms, including infant nurseries, selected
acute nursing areas, psychiatric bed areas (omit receptacles),
and ward treatment rooms
(b) Medication preparation areas
(c) Pharmacy dispensing areas
(d) Nurses ' stations (unless adequately lighted by corridor
luminaires)
(4) Additional specialized patient care task illumination and
receptacles, where needed
(5) Nurse call systems
(6) Blood, bone, and tissue banks
(7)*Telephone equipment rooms and closets
(8) Task illumination, select receptacles, and select power circuits
for the following areas:
(a) General care beds with at least one duplex receptacle
per patient bedroom, and task illumination as required
by the governing body of the health care facility
(b) Angiographic labs
(c) Cardiac catheterization labs
(d) Coronary care units
(e) Hemodialysis rooms or areas
(f) Emergency room treatment areas (select)
(g) Human physiology labs
(h) Intensive care units
(i) Postoperative recovery rooms (select)
(9) Additional task illumination, receptacles, and select power
circuits needed for effective facility operation, including
single-phase fractional horsepower motors, which are permitted
to be connected to the critical branch"
Tag No.: K0341
Based on observation and facility staff interview, the facility failed to ensure that one of one fire alarm systems was installed per NFPA 72, National Fire Alarm and Signaling Code, 2010 edition. The deficient practice has the potential to effect all facility patients, staff and visitors. The deficient practice could delay fire and emergency personnel response in the event of a fire. The facility census was 20
1. Observation on 2/28/18 during the facility tour, showed all exit corridors did not have complete smoke detector coverage.
During an interview on 2/28/18 at 1:44 P.M., the Director/Team Leader confirmed the observation.
National Fire Protection Association 101, 2012 edition, section 19.3.4.1 states:
"19.3.4.1 General. Health care occupancies shall be provided with a fire alarm system in accordance with Section 9.6."
Refer to NFPA 72, National Fire Alarm and Signaling Code, 2010 edition, sections 17.6.3 Location and Spacing and 17.6.3.3.1 Spacing for additional information.
Tag No.: K0351
Based on observation and interview, the facility failed to install a sprinkler system in accordance with the National Fire Protection Association 13, Standards for the Installation of Sprinkler Systems. These deficient practices affects all patients in the facility. The facility census was 20.
1. Observation on 2/28/18, during the facility tour, showed five of five elevator hoistway pits did not have sprinkler coverage. Observation showed all six elevators employ a hydraulic elevator lift mechanism that uses a petroleum-based hydraulic fluid, which is combustible.
During an interview on 2/28/18 at 1:47 P.M., the Director/Team Leader said that the elevator hoistway pits did not have sprinkler coverage.
Section 8.15.5.1* of NFPA 13 states: " Sidewall spray sprinklers shall be installed at the bottom of each elevator hoistway not more than 2 ft (0.61 m) above the floor of the pit.
* The sprinklers in the pit are intended to protect against fires caused by debris, which can accumulate over time. Ideally, the sprinklers should be located near the side of the pit below the elevator doors, where most debris accumulates. However, care should be taken that the sprinkler location does not interfere with the elevator toe guard, which extends below the face of the door opening.
ASME A17.1, Safety Code for Elevators and Escalators, allow the sprinklers within 2 ft (0.65 m) of the bottom of the pit to be exempted from the special arrangements of inhibiting waterflow until elevator recall has occurred.