Tag No.: A0700
The hospital failed to be constructed, arranged, and maintained to ensure the safety of the patient. Refer to A 709, Life Safety from Fire.
Tag No.: A0709
The hospital failed to comply with the provision of the 2000 (existing) Edition of the Life Safe Code of The National Fire Protection Association for the following reasons:
1. The facility failed to provide the required two (2) hour fire resistance rating for separation walls between non-conforming structures. Refer to K 011.
2. The facility failed to provide the required fire rated construction and/or a sprinkler system for structural elements. Refer to K012.
3. The facility failed to provide the required 1/2 hour fire resistance rating for corridor walls in a non-sprinkled facility. Refer to K017
4. The facility failed to provide the required 1/2 hour fire resistance rating for smoke barrier walls. Refer to K025.
5. The facility failed to provide the required one (1) hour fire resistance rating for hazardous areas in a non-sprinkled building. Refer to K029
6. The facility failed to provide the required two (2) master alarm panels for there bulk oxygen system. Refer to K140.