HospitalInspections.org

Bringing transparency to federal inspections

400 SE 4TH ST

EVANSVILLE, IN null

Fire Alarm System - Installation

Tag No.: K0341

Based on observation and interview, the facility failed to ensure at least 12 of 300 smoke detectors were not installed where air flow would adversely affect its operation. NFPA 72, 2010 edition, 17.7.6.3.2 requires that smoke detectors shall not be located directly in the airstream of supply registers. Section 17.7.4.1 requires in spaces served by air handling systems, detectors shall not be located where air flow prevents operation of the detectors. A.17.7.4.1 states detectors should not be located in a direct airflow or closer than 36 inches from an air supply diffuser or return air opening. This deficient practice could affect more than 10 patients, as well as staff and visitors.

Findings include:

Based on observations on 02/06/18 between 3:00 p.m. and 4:15 p.m. and 02/07/18 between 10:30 a.m. and 3:00 p.m. during a tour of the facility with the Director of Plant Operations, the following ceiling mounted smoke detectors were too close to air supply and return vents:
a. The smoke detector in the maintenance storage/locker room in the basement was within 8 inches of an air return vent
b. The smoke detector in the Financial Services office in the basement was within 8 inches of an air supply vent
c. The smoke detector in the 4th floor east-west corridor on the west side of the smoke barrier doors was within 12 inches of an air supply vent
d. The smoke detector in room 412 was within 12 inches of an air supply vent
e. The smoke detector in the 3rd floor Procedure Room was within 12 inches of an air supply vent
f. The smoke detector in the 3rd floor Pharmacy was within 6 inches of an air supply vent
g. The smoke detector in the 2nd floor corridor west of the nurses' station was within 6 inches of an air supply vent
h. The smoke detector room 211 was within 12 inches of an air supply vent
i. The smoke detector in the 1st floor Radiology Room was within 8 inches of an air supply vent
j. The smoke detector in the 1st floor Vending Machine room was within 12 inches of an air supply vent
k. Two smoke detectors in the 1st floor Triage Room hall were within 12 inches of two separate air supply vents
Based on interview at the time of each observation, the Director of Plant Operations agreed the smoke detector in question were all too close to air return and air supply vents.

Fire Alarm System - Out of Service

Tag No.: K0346

Based on record review and interview, the facility failed to provide a complete written policy for the protection of 50 of 50 patients indicating procedures to be followed in the event the fire alarm system has to be placed out of service for four hours or more in a twenty four hour period in accordance with LSC, Section 9.6.1.6. This deficient practice affects all occupants in the facility.

Findings include:

Based on record review on 02/06/18 at 11:40 a.m. with the Director of Plant Operations present, the facility provided fire watch documentation, however, it was incomplete. The plan failed to include the following:
a. The web link for contacting the Incident Reporting System located on the Indiana State Department of Health Gateway
b. The phone number for the local fire department
c. Contacting the facility's insurance carrier with phone number
d. The statement indicating the only duty the fire watch person has is the fire watch
e. The fire watch policy also did not include documentation to indicate the person conducting the fire watch has been properly trained. Based on an interview at the time of record review, the Director of Plant Operations agreed the fire watch policy lacked the previously mentioned information.

Sprinkler System - Maintenance and Testing

Tag No.: K0353

1. Based on record review, observation and interview; the facility failed to document sprinkler system inspections in accordance with NFPA 25 for 3 of 3 sprinkler systems (two dry systems and one wet system). NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2011 Edition, Section 5.2.4.1 states gauges on wet sprinkler systems shall be inspected monthly to ensure that they are in good condition and that normal water supply pressure is being maintained. Section 5.2.4.2 states gauges on dry pipe sprinkler systems shall be inspected weekly to ensure that normal air and water pressures are being maintained. Section 5.1.2 states valves and fire department connections shall be inspected, tested, and maintained in accordance with Chapter 13. Section 13.1.1.2 states Table 13.1.1.2 shall be utilized for inspection, testing and maintenance of valves, valve components and trim. Section 4.3.1 states records shall be made for all inspections, tests, and maintenance of the system and its components and shall be made available to the authority having jurisdiction upon request. This deficient practice could affect all patients, staff, and visitors in the facility.

Findings include:

Based on record review on 02/06/18 at 1:30 p.m. with the Director of Plant Operations present, there was documentation available from Ohio Valley Sprinkler that quarterly sprinkler inspections were performed on 03/28/17, 06/21/17, 09/21/17 and 12/20/17. Weekly dry sprinkler system gauge inspection documentation for 48 weeks of the most recent 52 week period was not available for review for the two dry sprinkler systems. Furthermore, monthly wet sprinkler system gauge inspection documentation for 8 months of the most recent 12 month period was not available for review. In addition, monthly inspection documentation for all three sprinkler system control valves for 8 months of the most recent 12 month period was also not available for review. Based on interview at the time of record review, the Director of Plant Operations indicated the facility performs regular visual sprinkler system inspections but does not document sprinkler system gauge and system control valves inspections and acknowledged sprinkler system gauge and control valve inspection documentation for the aforementioned weekly and monthly periods was not available for review. Based on observations with the Director of Plant Operations during a tour of the facility on 02/06/18 from 3:00 p.m. to 4:15 p.m. and on 02/07/18 from 10:30 a.m. to 3:00 p.m. the facility had at least 10 air or wet pressure gauges at the three sprinkler risers.

2. Based on observation and interview, the facility failed to ensure at least 20 of over 50 sprinkler heads in the old laundry room and maintenance area of the basement were free of corrosion. NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems at 5.2.1.1.1 requires sprinklers to be free of paint and corrosion. 5.2.1.1.2 requires any sprinkler that shows signs of paint or corrosion shall be replaced. This deficient practice could affect staff only.

Findings include:

Based on observations on 02/06/18 between 3:00 p.m. and 4:15 p.m. during a tour of the facility with the Director of Plant Operations, the following was noted:
a. 12 sprinkler heads in the old laundry room was covered with corrosion
b. 8 sprinkler head in the maintenance area were covered with corrosion
Based on interview at the time of observations, the Director of Plant Operations agreed the previously mentioned sprinkler heads were covered with corrosion.

Sprinkler System - Out of Service

Tag No.: K0354

Based on record review and interview, the facility failed to provide a written policy containing procedures to be followed for the protection of 50 of 50 residents in the event the automatic sprinkler system has to be placed out-of-service for 10 hours or more in a 24-hour period in accordance with LSC, Section 9.7.5. LSC 9.7.5 requires sprinkler impairment procedures comply with NFPA 25, 2011 Edition, the Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems. NFPA 25, 15.5.2 requires nine procedures that the impairment coordinator shall follow. This deficient practice could affect all occupants in the facility.

Findings include:

Based on record review on 02/06/18 at 11:40 a.m. with the Director of Plant Operations present, the facility provided fire watch documentation, however, it was incomplete. The plan failed to include the following:
a. The web link for contacting the Incident Reporting System located on the Indiana State Department of Health Gateway
b. The phone number for the local fire department
c. Contacting the facility's insurance carrier with phone number
d. The statement indicating the only duty the fire watch person has is the fire watch
e. The fire watch policy also did not include documentation to indicate the person conducting the fire watch has been properly trained. Based on an interview at the time of record review, the Director of Plant Operations agreed the fire watch policy lacked the previously mentioned information.

Subdivision of Building Spaces - Smoke Barrie

Tag No.: K0374

Based on observation and interview, the facility failed to ensure 1 of at least 7 sets of corridor doors would close to form a smoke resistant barrier. Centers for Medicare & Medicaid Services (CMS) requires sets of smoke barrier doors which swing in the same direction and equipped with an astragal to have a coordinator to ensure the door which must close first always closes first. This deficient practice could potentially affect patients, as well as staff and visitors on the 2nd floor.

Findings include:

Based on observation on 02/07/18 at 11:47 a.m. during a tour of the facility with the Director of Plant Operations, the set of smoke barrier doors near room 204 closed in the same direction with an astragal on one door. These doors and frame were not equipped with a coordinator to ensure that the door that's supposed to close first, does close first. Based on interview at the time of observation, the Director of Plant Operations said he was not aware the set of smoke barrier doors on the 2nd floor near room 204 required a coordinator.

Utilities - Gas and Electric

Tag No.: K0511

Based on observation and interview, the facility failed to ensure 3 of over 25 wet locations were provided with ground fault circuit interrupter (GFCI) protection against electric shock. NFPA 70, NEC 2011 Edition at 210.8 Ground-Fault Circuit-Interrupter Protection for Personnel, states, ground-fault circuit-interruption for personnel shall be provided as required in 210.8(A) through (C). The ground-fault circuit-interrupter shall be installed in a readily accessible location.
Informational Note: See 215.9 for ground-fault circuit interrupter protection for personnel on feeders.
(B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms
(2) Kitchens
(3) Rooftops
(4) Outdoors
Exception No. 1 to (3) and (4): Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable.
Exception No. 2 to (4): In industrial establishments only, where the conditions of maintenance and supervision ensure that only qualified personnel are involved, an assured equipment grounding conductor program as specified in 590.6(B)(2) shall be permitted for only those receptacle outlets used to supply equipment that would create a greater hazard if power is interrupted or having a design that is not compatible with GFCI protection.
(5) Sinks - where receptacles are installed within 1.8 m (6 ft.) of the outside edge of the sink.
Exception No. 1 to (5): In industrial laboratories, receptacles used to supply equipment where removal of power would introduce a greater hazard shall be permitted to be installed without GFCI protection.
Exception No. 2 to (5): For receptacles located in patient bed locations of general care or critical care areas of health care facilities other than those covered under
210.8(B)(1), GFCI protection shall not be required.
(6) Indoor wet locations
(7) Locker rooms with associated showering facilities
(8) Garages, service bays, and similar areas where electrical
diagnostic equipment, electrical hand tools.
NFPA 70, 517-20 Wet Locations, requires all receptacles and fixed equipment within the area of the wet location to have ground-fault circuit interrupter (GFCI) protection. Note: Moisture can reduce the contact resistance of the body, and electrical insulation is more subject to failure. This deficient practice could affect staff only.

Findings include:

Based on observations on 02/07/18 between 10:30 a.m. and 3:00 p.m. during a tour of the facility with the Director of Plant Operations, the following was noted:
a. There was one electric receptacle within two feet of the sink in the third floor staff locker room. The electric receptacle was not provided with ground fault circuit interrupters (GFCI). This was confirmed when tested with a GFCI testing device
b. There was one electric receptacle within two feet of the sink in the second floor staff lounge. The electric receptacle was not provided with ground fault circuit interrupters (GFCI). This was confirmed when tested with a GFCI testing device
c. There was one electric receptacle within two feet of the sink in the second floor Day Room. The electric receptacle was not provided with ground fault circuit interrupters (GFCI). This was confirmed when tested with a GFCI testing device
Based on interview at the time of each observation, the Director of Plant Operations agreed the receptacles in the previously mentioned rooms were not GFCI protected.

Evacuation and Relocation Plan

Tag No.: K0711

Based on record review and interview, the facility failed to provide a complete facility specific written fire safety plan for the protection of 50 of 50 patients to accurately address all life safety systems, plus a system addressing all items required by NFPA 101, 2012 edition, Section 19.7.2.2. LSC 19.7.2.2 requires a written health care occupancy fire safety plan that shall provide for the following:
(1) Use of alarms
(2) Transmission of alarm to fire department
(3) Emergency phone call to fire department
(4) Response to alarms
(5) Isolation of fire
(6) Evacuation of immediate area
(7) Evacuation of smoke compartment
(8) Preparation of floors and building for evacuation
(9) Extinguishment of fire
Section 19.2.3.4(4) states any required aisle or corridor shall not be less than 48 inches in clear width where serving as means of egress from patient sleeping rooms. Projections into the required width shall be permitted for wheeled equipment provided the relocation of wheeled equipment during a fire or similar emergency is addressed in the written fire safety plan and training program for the facility. The wheeled equipment is limited to:
i. Equipment in use and carts in use
ii. Medical emergency equipment not in use
iii. Patient lift and transport equipment
This deficient practice could affect all occupants in the event of an emergency.

Findings include:

Based on a review of the Fire Plan on 02/06/18 at 11:48 a.m. with the Director of Plant Operations present, the fire safety plan did not address the following issues:
a. The transmission of the alarm to the fire department
b. A back up call to the fire department (911) after the fire alarm system has been activated
c. Isolation of the fire
d. The evacuation of the smoke compartment
e. Location of smoke/fire barriers
f. The use of the K-class fire extinguisher in the kitchen in relationship with the use of the kitchen overhead extinguishing system
Based on interview at the time of record review, the Director of Plant Operations agreed that the fire plan reviewed was not a complete fire safety plan.

Electrical Systems - Essential Electric Syste

Tag No.: K0916

Based on observation and interview, the facility failed to ensure 1 of 1 emergency generator was provided with an alarm annunciator in a location readily observed by operating personnel at a regular work station such as a nurses' stations. NFPA 99, 2012 Edition, Health Care Facilities Code, at 6.4.1.1.17 requires a remote annunciator that is storage battery powered shall be provided to operate outside of the generating room in a location readily observed by operating personnel at a regular work station. The annunciator shall be hard-wired to indicate alarm conditions of the emergency or auxiliary power source as follows:
(1) Individual visual signals shall indicate:
a. When the emergency or auxiliary power source is operating to supply power to load.
b. When the battery charger is malfunctioning.
(2) Individual visual signals plus a common audible signal to warn of an engine-generator alarm condition shall indicate:
a. Low lubricating oil pressure.
b. Low water temperature.
c. Excessive water temperature.
d. Low fuel when the main fuel storage tank contains less than a 4-hour operating supply.
e. Overcrank (failed to start).
f. Overspeed.
Where a regular work station will be unattended periodically, an audible and visual derangement signal, appropriately labeled, shall be established at a continuously monitored location. This derangement signal shall activate when any of the conditions in 6.4.1.1.17(1) and (2) occur but need not display these conditions individually. This deficient practice could affect all patients, as well as visitors and staff in the facility.

Findings include:

Based on interview during record review on 02/06/18 at 3:00 p.m., the Director of Plant Operations said the facility has an emergency generator. When asked, the Director of Plant Operations said there was no remote alarm annunciator panel for the generator at a 24 hour station, such as a nurses' station. This was confirmed during a tour of the facility with the Director of Plant Operations on 02/06/18 between 3:00 p.m. and 4:15 p.m. and on 02/07/18 between 10:30 a.m. and 3:00 p.m., there was no remote alarm annunciator panel for the generator at any nurses' station.