Tag No.: K0351
Based on observations during the survey walk of the facility on the afternoon of 12/19/2016 with the administrator, the facility's fire sprinkler system did not comply with NFPA 13. No sprinkler head existed at vestibule and ultrasound closet.
Tag No.: K0400
Based on observations during the survey walk of the facility on the afternoon of 12/19/2016 with the administrator, the facility failed to maintain the facility. Ice machine for dietary was located in an exterior room, where dust and insects could enter.
Tag No.: K0712
Based on observations during the survey walk of the facility on the afternoon of 12/19/2016 with the administrator, proper fire drills were not being performed. Upon conducting fire drills, the facility shall pull a fire station to include the transmission of a fire alarm signal.