Bringing transparency to federal inspections
Tag No.: K0029
Based on observation and interview with the Facilities Director during a tour of the facility, it was observed that the facility did not maintain the proper fire-rated separations for hazardous areas. Specifically:
On 11/16/10 at 10:00am, there was an unsealed penetration through the mechanical closet on 3 North.
Tag No.: K0039
Based on observation and interview with the Facilities Director during a tour of the facility, the hospital did not maintain the exits in a clear and unobstructed manner. Specifically:
On 11/17/10 at 11:00 am, there were three IV poles stored in the exit corridor from the first floor Massry building.
Tag No.: K0056
Based on observation and interview with the Facilities Director during a tour of the facility , the sprinkler system was not installed and maintained properly. Specifically:
On 11/17/10 at 10:30am in Central Sterile Supply, two sprinkler heads were installed above the level of the suspended ceiling.
On 11/16/10 at 4:00pm in the Radiology Department, two corridor storage closets had items on the top shelves stored less than 18 inches below the sprinkler heads.
Tag No.: K0077
Based on observation and interview with the Facilities Director during a tour of the facility, it was determined that the piped-in hospital medical gas system does not comply with NFPA 99, Chapter 4.
Specifically, on 11/15/10 at 2:30pm, during a tour of the 6th and 5th floors, it was observed that the labels for the medical gas controls do not accurately reflect which areas or rooms the gas shut-offs control. In some instances the shut-offs were disconnected, but still labeled as operable.